Bryant Electric 594D User Manual

ELECTRIC  
AIR CONDITIONER  
Model 594D (60 Hz)  
Sizes 018 thru 060  
WIDE RANGE OF SIZES—Available in 7 nominal sizes from 018  
through 060 to meet the needs for residential and light commercial  
applications.  
WEATHER-PROTECTIVE CABINET—Steel is galvanized, then  
coated with a layer of zinc phosphate to which a coat of modified  
polyester powder coating is applied and baked on. This provides  
each unit with a hard, smooth finish that will last for many years.  
All screws on cabinet exterior are ceramic coated for a long-last-  
ing, rust-resistant, quality appearance.  
TOTALLY ENCLOSED FAN MOTOR—Means greater reliability  
under rain conditions and dependable performance for many  
years.The permanent-split capacitor type motor was designed for  
optimum efficiency. Then, under extreme conditions, the motor  
was tested and qualified to help ensure the greatest reliability.  
UNIT DESIGN—Copper tube, enhanced aluminum fin coil is  
designed for optimum heat transfer.Vertical air discharge carries  
sound and hot condenser air up and away from adjacent patio  
areas and foliage. Heat pump style base pan for easy removal of  
water, dirt, and leaves.  
APPLICATION VERSATILITY—The 594D can be combined  
with a wide variety of evaporator coils and blower packages to  
provide quiet, dependable comfort. Unit can be installed on a  
roof or at ground level on a slab.  
EXTERNAL SERVICEVALVES—Both service valves are brass,  
back seating type with sweat connections. Valves are externally  
located so refrigerant tube connections can be made quickly and  
easily. Each valve has a service port for ease of checking oper-  
ating refrigerant pressures.  
EASY SERVICEABILITY—One panel provides access to elec-  
trical controls and compressor. Removal of wire dome grille  
gives access to fan motor, while removal of top gives access to  
coil.  
COMPRESSOR PROTECTION—Each model is protected with  
internal temperature- and current-sensitive overloads. An inter-  
nal pressure relief valve provides high-pressure protection to the  
refrigerant system.  
Model 594D Energy-Efficient Air Conditioners incorporate inno-  
vative technology to provide quiet, reliable summer cooling per-  
formance.Built into these units are the features most desired by  
homeowners today, including SEER ratings of up to 12.0 when  
used with components as designated by manufacturer.All mod-  
els are listed with UL, c-UL, ARI, CEC, and CSA-EEV.  
AEROQUIET FAN SYSTEM—Allows air to move through the  
unit more easily which lowers sound levels and improves overall  
efficiency.  
AVAILABLE OPTIONS  
SCROLL COMPRESSOR—All units feature the scroll compres-  
sor. This compressor is significantly more efficient than conven-  
tional compressors. Due to the simplicity of its design, it offers  
improved reliability. Each compressor is mounted on rubber iso-  
lators for additional sound reduction. Continuous operation is  
approved down to 55°F (12.8°C) in the cooling mode. (See cool-  
ing performance tables.)  
ELECTRICAL RANGE—All units are offered in 208/230-volts,  
single phase.  
HEAVY DUTY INLET GRILLE—The DuraGuard™ coil pro-  
tector, made of a coated steel wire grid with vertical 3/8 in.  
spacing, is designed to help protect the coil from inclement  
weather, vandalism, and incidental damage. It provides pro-  
tection while not restricting airflow and maintaining ease of  
coil inspection and cleaning.  
LIMITED WARRANTY—Standard 1-year warranty on all parts,  
with an additional 9-year warranty on the compressor.  
Form No. PDS 594D.18.7  
RECOMMENDED TUBE DIAMETERS  
LIQUID TUBE DIAMETER (IN.)  
VAPOR TUBE DIAMETER (IN.)  
UNIT  
SIZE  
0 to 50 Ft  
Tube Length  
0 to 50 Ft  
Tube Length  
Long-Line Applications*  
(Maximum Diameter)  
Long-Line Applications*  
018, 024  
030, 036  
042, 048  
060  
5/8  
3/4  
3/4  
7/8  
3/8  
3/8  
7/8  
1-1/8  
1-1/8  
1-1/8  
* For tube sets between 50 and 175 ft, consult Residential Split System Long-Line Application Guideline.  
CHECK-FLO-RATER®  
PISTON*  
UNIT SIZE-SERIES  
IDENTIFICATION NO.  
018, E  
55  
59  
67  
73  
78  
84  
93  
024, E  
030, E  
036, E  
042, E  
048, E,F  
060, E  
* Piston listed is for any approved non-capillary tube coil combination.  
Piston is shipped with outdoor unit and must be installed in an approved  
indoor coil.  
SOUND POWER (dBA)  
OCTAVE BAND CENTER FREQUENCY (Hz)  
UNIT  
SIZE  
SOUND  
LEVEL (dBA)  
125  
54.5  
51.5  
57.0  
59.0  
58.0  
60.0  
61.5  
250  
63.0  
61.0  
64.0  
66.0  
65.0  
64.0  
64.5  
500  
65.5  
62.5  
67.0  
67.0  
67.5  
68.5  
69.0  
1000  
66.0  
65.5  
69.0  
69.5  
69.0  
68.5  
70.0  
2000  
63.5  
62.0  
64.0  
66.5  
65.5  
67.5  
68.0  
4000  
59.0  
58.5  
60.0  
62.5  
61.0  
64.5  
66.0  
8000  
51.5  
52.5  
52.5  
56.0  
54.0  
59.5  
60.5  
018  
024  
030  
036  
042  
048  
060  
72  
74  
74  
76  
76  
78  
78  
P
REGISTERED QUALITY SYSTEM  
CERTIFICATION APPLIES ONLY  
WHEN THE COMPLETE SYSTEM  
IS LISTED WITH ARI  
—3—  
SPECIFICATIONS  
UNIT SIZE - SERIES  
OPERATING WT (Lb)  
018-E  
138  
024-E  
143  
030-E  
146  
036-E  
200  
ELECTRICAL  
Unit Volts—Hertz—Phase  
Operating Voltage Range*  
Compressor— Rated Load Amps  
Locked Rotor Amps  
208/230—60—1  
208/230—60—1  
208/230—60—1  
208/230—60—1  
187—253  
8.9  
187—253  
11.4  
56.0  
0.5  
187—253  
13.7  
72.5  
0.8  
187—253  
16.0  
88.0  
1.1  
41.0  
0.5  
Condenser Fan Motor—Full Load Amps  
Min Unit Ampacity for Wire Sizing  
Min Wire Size (60°C Copper) AWG†  
Min Wire Size (75°C Copper) AWG†  
Max Wire Length (60°C) (Ft)‡  
Max Wire Length (75°C) (Ft)‡  
Max Branch Circuit Fuse Size**  
COMPRESSOR AND REFRIGERANT  
Compressor—Manufacturer & Type  
Temperature & Current Protection  
Refrigerant—R-22 Amount (Lb)  
CONDENSER COIL AND FAN  
Coil Face Area (Sq Ft)  
11.6  
14  
14.8  
14  
17.9  
14  
21.1  
12  
14  
14  
14  
12  
61  
53  
56  
66  
58  
50  
53  
63  
20  
20  
25  
30  
Copeland Scroll  
Internal Line Break  
4.00  
7.27  
4.25  
4.50  
5.53  
12.0  
8.8  
Fins per In.—Rows—Circuits  
Fan Motor—HP, Type, & RPM  
Volts—Hertz—Phase  
20—1—1  
25—1—2  
1/12 PSC & 1100  
1/10 PSC & 1100  
208/230—60—1  
1/5 PSC & 825  
3000  
Condenser Airflow (CFM)  
OPTIONAL EQUIPMENT  
Support Feet Kit  
1700  
2000  
KSASF0101AAA  
KAACF0601SML  
KAATD0101TDR  
Coastal Filter  
KAACF0201MED  
Time-Delay Relay  
Cycle Protector  
KSACY0101AAA  
KAACH1201AAA  
KSAHS1501AAA  
KAACS0201PTC  
Crankcase Heater  
Start Assist—Capacitor/Relay Type  
Start Assist—PTC Type  
TXV Kit (RPB)  
KAATX0201RPB  
KAATX0301RPB  
KAATX0401RPB  
KAATX0501RPB  
TXV Kits (Hard Shutoff)  
Low-Pressure Switch  
KSATX0601HSO  
KAALP0101LPS  
KSAHI0101HPS  
P502-8083S (RCD)  
KAAFT0101AAA  
KAALS0101LLS  
KAAWS0101AAA  
KSALA0201R22  
P251-0083 (RCD)  
32LT660004 (RCD)  
High-Pressure Switch  
Filter Drier  
Evaporator Freeze Thermostat††  
Liquid-Line Solenoid Valve  
Winter Start Control††  
Low-Ambient Kit  
Low-Ambient Controller  
MotorMaster® Control‡‡  
Ball Bearing Fan Motor  
HC34GE232 (RCD)  
HC38GE231 (RCD)  
Thermostat, Auto Changeover,  
Non-Programmable, °F/°C,  
1-Stage Heat, 1-Stage Cool  
TSTATBBNAC01-B  
TSTATBBPAC01-B  
TSTATBBBAC01-B  
Thermostat, Auto Changeover,  
7-Day Programmable, °F/°C,  
1-Stage Heat, 1-Stage Cool  
Builder’s Thermostat, Manual  
Changeover, Non-Programmable,  
°F/°C, 1-Stage Heat, 1-Stage Cool  
Thermidistat™ Control—Programmable/  
Non-Programmable Thermostat with  
Humidity Control  
TSTATBBPRH01-B  
TSTATXXSEN01-B  
Outdoor Air Temperature Sensor  
Backplate for Non-Programmable  
Thermostat  
TSTATXXNBP01  
TSTATXXBBP01  
TSTATXXPBP01  
Backplate for Builder’s Thermostat  
Backplate for Programmable Thermostat  
Thermostat Conversion Kit (4 to 5 wire)  
— 10 Pack  
TSTATXXCNV10  
See notes on page 5.  
—4—  
SPECIFICATIONS Continued  
UNIT SIZE - SERIES  
OPERATING WT (Lb)  
042-E  
213  
048-E/F  
060-E  
287  
247  
ELECTRICAL  
Unit Volts—Hertz—Phase  
Operating Voltage Range*  
Compressor— Rated Load Amps  
Locked Rotor Amps  
208/230—60—1  
208/230—60—1  
187—253  
23.7/21.3  
129.0/137.0  
1.4  
208/230—60—1  
187—253  
20.0  
104.0  
1.1  
187—253  
28.8  
169.0  
1.4  
Condenser Fan Motor—Full Load Amps  
Min Unit Ampacity for Wire Sizing  
Min Wire Size (60°C Copper) AWG†  
Min Wire Size (75°C Copper) AWG†  
Max Wire Length (60°C) (Ft)‡  
Max Wire Length (75°C) (Ft)‡  
Max Branch Circuit Fuse Size**  
COMPRESSOR AND REFRIGERANT  
Compressor—Manufacturer & Type  
Temperature & Current Protection  
Refrigerant—R-22 Amount (Lb)  
CONDENSER COIL AND FAN  
Coil Face Area (Sq Ft)  
26.1  
10  
31.0/28.0  
8/10  
37.4  
8
10  
10  
8
96  
71  
104  
99  
91  
68  
40  
50/40  
60  
Copeland Scroll  
Internal Line Break  
6.34  
6.68  
9.25  
15.2  
18.3  
Fins per In.—Rows—Circuits  
Fan Motor—HP, Type, & RPM  
Volts—Hertz—Phase  
25—1—3  
25—1—4  
1/5 PSC & 825  
3000  
1/4 PSC & 1100  
3300  
208/230—60—1  
Condenser Airflow (CFM)  
OPTIONAL EQUIPMENT  
Support Feet Kit  
KSASF0101AAA  
KAACF0201MED  
KAATD0101TDR  
Coastal Filter  
Time-Delay Relay  
Cycle Protector  
KSACY0101AAA  
Standard  
Crankcase Heater  
KAACH1201AAA  
Start Assist—Capacitor/Relay Type  
Start Assist—PTC Type  
TXV Kit (RPB)  
KSAHS1501AAA  
KSAHS1601AAA  
KAATX0701RPB  
KAACS0201PTC  
KAATX0601RPB  
KAATX0501RPB  
KSATX0601HSO  
TXV Kits (Hard Shutoff)  
Low-Pressure Switch  
KSATX0701HSO  
KAALP0101LPS  
KSAHI0101HPS  
P502-8163S (RCD)  
KAAFT0101AAA  
KAALS0101LLS  
KAAWS0101AAA  
KSALA0201R22  
P251-0083 (RCD)  
32LT660004 (RCD)  
High-Pressure Switch  
Filter Drier  
Evaporator Freeze Thermostat††  
Liquid-Line Solenoid Valve  
Winter Start Control††  
Low-Ambient Kit  
Low-Ambient Controller  
MotorMaster® Control‡‡  
Ball Bearing Fan Motor  
HC38GE231 (RCD)  
HC40GE232 (RCD)  
Thermostat, Auto Changeover,  
Non-Programmable, °F/°C,  
1-Stage Heat, 1-Stage Cool  
TSTATBBNAC01-B  
TSTATBBPAC01-B  
TSTATBBBAC01-B  
Thermostat, Auto Changeover,  
7-Day Programmable, °F/°C,  
1-Stage Heat, 1-Stage Cool  
Builder’s Thermostat, Manual  
Changeover, Non-Programmable,  
°F/°C, 1-Stage Heat, 1-Stage Cool  
Thermidistat™ Control—Programmable/  
Non-Programmable Thermostat with  
Humidity Control  
TSTATBBPRH01-B  
TSTATXXSEN01-B  
Outdoor Air Temperature Sensor  
Backplate for Non-Programmable  
Thermostat  
TSTATXXNBP01  
TSTATXXBBP01  
TSTATXXPBP01  
Backplate for Builder’s Thermostat  
Backplate for Programmable Thermostat  
Thermostat Conversion Kit (4 to 5 wire)  
— 10 Pack  
TSTATXXCNV10  
*
Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.  
Copper wire must be used from service disconnect to unit.  
If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).  
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70)  
Article 336-26.  
Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2 percent.  
All motors/compressors contain internal overload protection.  
** Time-delay fuse.  
†† Use with Low-Ambient Controller.  
‡‡ Fan motor with ball bearings required.  
—5—  
ACCESSORY USAGE GUIDELINE  
REQUIRED FOR  
LOW-AMBIENT  
APPLICATIONS  
(Below 55°F)  
REQUIRED FOR  
REQUIRED FOR  
SEA COAST  
APPLICATIONS  
(Within 2 Miles)  
LONG-LINE  
APPLICATIONS*  
(Over 50 Ft)  
ACCESSORY  
Crankcase Heater  
Yes  
Yes  
Yes†  
No  
Yes  
No  
No  
No  
No  
No  
No  
No  
Evaporator Freeze Thermostat  
Winter Start Control  
Accumulator  
Compressor Start Assist  
Capacitor and Relay  
Yes  
Yes  
Yes  
No  
No  
No  
Low-Ambient Controller  
or  
MotorMaster® Control  
Wind Baffle  
Coastal Filter  
Support Feet  
See Low-Ambient Instructions  
No  
No  
No  
No  
Yes  
No  
Recommended  
Recommended  
Liquid-Line Solenoid Valve  
See Long-Line  
Application  
Guideline  
or  
No  
No  
No  
Hard Shutoff TXV  
Ball Bearing Fan Motor  
Yes  
No  
* For tubing line sets between 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline.  
† Only when low-pressure switch is used.  
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)  
1. Ball Bearing Fan Motor  
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.  
SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.  
2. Coastal Filter  
A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from corrosive atmosphere without restricting airflow.  
SUGGESTED USE: In geographic areas where salt damage could occur.  
In areas with high pollution levels.  
3. Compressor Start Assist—Capacitor/Relay Type  
Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.  
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.  
Installations where outdoor design temperature exceeds 105°F (40.6°C).  
Replacement installations with hard shutoff expansion valve on indoor coil.  
Installations where Liquid-Line Solenoid Valve has been added.  
4. Compressor Start Assist—PTC Type  
Solid state electrical device which gives a ‘‘soft’’ boost to compressor motor at each start-up.  
SUGGESTED USE: Installations with marginal power supply.  
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.  
5. Crankcase Heater  
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication  
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.  
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.  
When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with Low-Ambient Controller.  
All commercial installations.  
6. Cycle Protector  
Solid state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has  
been interrupted for any reason, including normal room thermostat cycling.  
SUGGESTED USE: Installations in areas where power interruptions are frequent.  
Where user is likely to “play” with the room thermostat.  
All commercial installations.  
Installations where interconnecting tube length exceeds 50 ft.  
High-rise applications.  
7. Evaporator Freeze Thermostat  
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.  
SUGGESTED USE: All units where Winter Start Control has been added. Use with Low-Ambient Controller.  
8. Filter Drier  
A device for removing contaminants from refrigerant circulating in an air conditioner: 1 direction flow.  
SUGGESTED USE: All split-system air conditioners.  
9. High-Pressure Switch  
Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10  
psig and resets at 298 ± 20 psig. Provides protection against compressor damage due to loss of outdoor airflow. To prevent rapid compressor recycling,  
Cycle Protector can be used with this switch.  
SUGGESTED USE: Installations exposed to very ‘‘dirty’’ outdoor air.  
Installations where condenser inlet air temperature exceeds 125°F (51.7°C).  
10. Liquid-Line Solenoid Valve (LSV)  
An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) which stops and starts refrigerant  
liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.  
Note: Compressor Start Assist—Capacitor/Relay Type must also be used. Do not use with hard shutoff TXV.  
SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.  
In certain long-line applications. Refer to Residential Split System Long-Line Application Guideline.  
—6—  
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued  
11. Low-Ambient Controller  
Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle  
the outdoor fan motor in order to maintain condensing temperature within normal operating limits (approximately 100°F high and 60°F low).The control will  
maintain working head pressure at low-ambient temperatures down to 0°F when properly installed.  
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).  
12. Low-Pressure Switch  
Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27  
psig. Prevents indoor coil freeze-up due to loss of indoor airflow. Provides protection against compressor damage due to loss of refrigerant charge. To  
prevent rapid compressor recycling, Cycle Protector can be used with this switch.  
SUGGESTED USE: Where indoor coil is exposed to ‘‘dirty’’ air.  
All commercial installations.  
13. MotorMaster® Control  
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing  
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F, it maintains condensing temperature at 100°F ± 10°F.  
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F.  
All commercial installations.  
14. Outdoor Air Temperature Sensor  
A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.  
SUGGESTED USE: All corporate programmable thermostats.  
15. Support Feet  
Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base,  
minimizing corrosion.  
SUGGESTED USE: Coastal installations.  
Windy areas or where debris is normally circulating.  
Rooftop installations.  
16. Thermostatic Expansion Valve (TXV)  
A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the  
evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB type valves are available.  
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.  
Required for use on all zoning systems.  
17. Time-Delay Relay  
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.  
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.  
Required for use on all zoning systems.  
18. Winter Start Control  
An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load conditions.  
SUGGESTED USE: All air conditioners where Low-Ambient Controller has been added.  
—7—  
COMBINATION RATINGS  
SEER  
FACTORY  
SUPPLIED  
ENHANCE-  
MENT  
BRYANT GAS  
FURNACE OR  
STANDARD ACCESSORY ACCESSORY  
UNIT  
SIZE-SERIES  
INDOOR  
MODEL  
TOT. CAP.  
BTUH  
RATING  
TDR†  
TXV‡  
EERA  
CK5A/CK5BA024*  
CC5A/CD5AA018  
CC5A/CD5AA024  
CC5A/CD5AW024  
CE3AA024  
17,600  
17,200  
17,600  
17,600  
17,600  
17,600  
17,200  
17,600  
16,800  
17,600  
17,600  
17,000  
17,600  
17,000  
18,000  
18,000  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
TDR  
10.50  
10.50  
10.50  
10.50  
10.50  
10.50  
10.50  
10.50  
11.00  
11.00  
11.00  
10.50  
10.50  
10.50  
12.50  
12.50  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
10.60  
10.45  
10.60  
10.60  
10.60  
10.60  
10.45  
10.60  
10.40  
10.75  
10.60  
10.70  
10.65  
10.45  
12.05  
12.10  
CK3BA024  
CK5A/CK5BA018  
CK5A/CK5BW024  
F(A,B)4AN(F,C)018  
F(A,B)4AN(F,C)024  
FC4BNF024  
FF1(B,C,D)NA018  
FF1(B,C,D)NA024  
FG3AAA024  
FK4CNF001  
FK4CNF002  
TDR  
TDR&TXV  
TDR  
TDR  
NONE  
TDR&TXV  
TDR&TXV  
11.00  
11.00  
11.00  
11.00  
018-E  
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE  
CC5A/CD5AA018  
CC5A/CD5AA024  
CK5A/CK5BA018  
CK5A/CK5BA024  
17,000  
17,600  
17,000  
17,600  
TDR  
TDR  
TDR  
TDR  
12.50  
13.00  
12.50  
13.00  
12.50  
13.00  
12.50  
13.00  
11.40  
11.80  
11.40  
11.80  
COILS + 355MAV042060 VARIABLE SPEED FURNACE  
CC5A/CD5AW024  
CK5A/CK5BW024  
17,600  
17,600  
TDR  
TDR  
13.00  
13.00  
13.00  
13.00  
11.60  
11.60  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CC5A/CD5AW024  
CK5A/CK5AW024  
17,600  
17,600  
TDR  
TDR  
13.00  
13.00  
13.00  
13.00  
11.70  
11.70  
CC5A/CD5AA030*  
CC5A/CD5AA024  
CC5A/CD5AW024  
CC5A/CD5AW030  
CE3AA024  
23,000  
23,000  
23,000  
23,200  
23,000  
23,200  
23,000  
23,000  
23,000  
23,000  
23,000  
23,000  
23,200  
23,000  
23,400  
23,000  
23,400  
23,000  
23,400  
22,600  
24,000  
24,200  
24,400  
NONE  
NONE  
10.80  
10.80  
10.80  
10.80  
10.80  
11.00  
10.80  
10.80  
10.80  
10.80  
10.80  
10.80  
10.80  
11.00  
11.40  
11.00  
11.40  
11.00  
11.30  
10.50  
12.50  
12.70  
13.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.30  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.30  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.40  
9.80  
9.70  
9.70  
9.80  
9.80  
9.80  
9.80  
9.70  
9.80  
9.70  
9.80  
9.70  
9.80  
9.80  
10.00  
9.80  
10.00  
9.70  
9.90  
9.60  
10.95  
11.05  
11.30  
NONE  
NONE  
NONE  
CE3AA030  
NONE  
CF5AA024  
NONE  
CK3BA024  
NONE  
CK3BA030  
NONE  
CK5A/CK5BA024  
CK5A/CK5BA030  
CK5A/CK5BW024  
CK5A/CK5BW030  
F(A,B)4AN(F,C)024  
F(A,B)4AN(F,C)030  
FC4BNF024  
NONE  
NONE  
NONE  
NONE  
TDR  
TDR  
TDR & TXV  
TDR & TXV  
TDR  
FC4BNF030  
FF1(B,C,D))NA024  
FF1(B,C,D))NA030  
FG3AAA024  
11.00  
11.30  
11.00  
TDR  
NONE  
TDR & TXV  
TDR & TXV  
TDR & TXV  
024-E  
11.00  
FK4CNF001  
FK4CNF002  
FK4CNF003  
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE  
CC5A/CD5AA030  
CE3AA030  
CK5A/CK5BA030  
23,200  
23,200  
23,200  
TDR  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
12.00  
12.00  
10.75  
10.85  
10.75  
COILS + 355MAV042040 VARIABLE SPEED FURNACE  
CC5A/CD5AA030  
CK5A/CBA5030  
23,200  
23,200  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
10.70  
10.70  
COILS + 355MAV042060 VARIABLE SPEED FURNACE  
CC5A/CD5AA030  
CK5A/CK5BA030  
23,200  
23,200  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
10.70  
10.70  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CC5A/CD5AA030  
CK5A/CK5BA030  
23,200  
23,200  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
10.70  
10.70  
CC5A/CD5AA036*  
CC5A/CD5AA030  
CC5A/CD5AW030  
CD5AW036  
29,000  
28,200  
28,200  
29,000  
28,400  
28,800  
29,000  
28,200  
29,000  
28,200  
29,000  
28,200  
29,000  
28,200  
28,600  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
TDR  
10.80  
10.40  
10.40  
10.80  
10.50  
10.60  
10.60  
10.40  
10.80  
10.40  
10.80  
10.50  
10.80  
11.00  
10.80  
11.00  
10.60  
10.60  
11.00  
10.80  
11.00  
11.00  
10.60  
11.00  
10.60  
11.00  
10.60  
11.00  
11.00  
10.60  
10.60  
11.00  
10.80  
11.00  
11.00  
10.60  
11.00  
10.60  
11.00  
10.60  
11.00  
11.00  
10.80  
9.60  
9.30  
9.30  
9.60  
9.40  
9.50  
9.55  
9.30  
9.60  
9.30  
9.60  
9.30  
9.60  
9.45  
9.35  
CE3AA030  
CE3AA036  
CF5AA036  
030-E  
CK3BA030  
CK3BA036  
CK5A/CK5BA030  
CK5A/CK5BA036  
CK5A/CK5BW030  
CK5A/CK5BW036  
F(A,B)4AN(F,C)030  
F(A,B)4AN(F,C)036  
TDR  
See notes on page 11.  
—8—  
COMBINATION RATINGS Continued  
SEER  
FACTORY  
SUPPLIED  
ENHANCE-  
MENT  
BRYANT GAS  
FURNACE OR  
STANDARD ACCESSORY ACCESSORY  
UNIT  
SIZE-SERIES  
INDOOR  
MODEL  
TOT. CAP.  
BTUH  
RATING  
TDR†  
TXV‡  
EERA  
FC4BNF030  
FC4BNF036  
28,200  
28,600  
28,400  
28,600  
29,200  
29,400  
29,600  
TDR & TXV  
TDR & TXV  
TDR  
11.00  
10.80  
11.00  
10.50  
11.50  
11.80  
12.00  
9.45  
9.35  
FF1(B,C,D)NA030  
FG3AAA036  
FK4CNF001  
11.00  
10.80  
9.40  
NONE  
10.80  
9.40  
TDR & TXV  
TDR & TXV  
TDR & TXV  
10.05  
10.10  
10.55  
FK4CNF002  
FK4CNF003  
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE  
CC5A/CD5AA036  
CE3AA036  
CK5A/CK5BA036  
29,400  
29,000  
29,400  
TDR  
TDR  
TDR  
12.20  
12.00  
12.00  
12.20  
12.00  
12.00  
10.45  
10.30  
10.45  
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE  
030-E  
CC5A/CD5AA036  
CE3AA036  
CK5A/CK5BA036  
29,400  
29,000  
29,400  
TDR  
TDR  
TDR  
12.20  
12.00  
12.00  
12.20  
12.00  
12.00  
10.45  
10.30  
10.45  
COILS + 355MAV042040 VARIABLE SPEED FURNACE  
CC5A/CD5AA036  
CK5A/CK5BA036  
29,400  
29,400  
TDR  
TDR  
12.00  
11.80  
12.00  
11.80  
10.40  
10.40  
COILS + 355MAV042060 VARIABLE SPEED FURNACE  
CC5A/CD5A036  
CK5A/CK5BA036  
29,400  
29,400  
TDR  
TDR  
12.00  
11.80  
12.00  
11.80  
10.40  
10.40  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CC5A/CD5AA036  
CK5A/CK5BA036  
29,400  
29,400  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
10.40  
10.40  
CC5A/CD5AA042*  
CC5A/CD5AA036  
CC5A/CD5AW042  
CD5AW036  
35,000  
35,000  
34,800  
35,000  
34,400  
35,000  
35,000  
35,000  
35,000  
35,000  
35,000  
35,000  
34,800  
35,000  
34,400  
36,600  
34,400  
35,000  
36,000  
34,200  
36,200  
34,600  
34,800  
35,000  
36,000  
NONE  
NONE  
11.00  
11.00  
11.00  
11.00  
10.80  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.20  
11.00  
12.00  
11.00  
11.20  
11.50  
10.80  
13.00  
11.50  
11.50  
12.00  
12.50  
11.20  
11.20  
11.20  
11.20  
11.00  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.00  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.20  
11.00  
10.15  
10.15  
10.05  
10.15  
10.05  
10.20  
10.10  
10.15  
10.15  
10.15  
10.15  
10.15  
10.05  
10.10  
9.80  
NONE  
NONE  
CE3AA036  
NONE  
CE3AA042  
NONE  
CF5AA036  
NONE  
CK3BA036  
NONE  
CK3BA042  
NONE  
CK5A/CK5BA036  
CK5A/CK5BA042  
CK5A/CK5BW036  
CK5A/CK5BW042  
F(A,B)4AN(F,B,C))042  
F(A,B)4AN(F,C)036  
FC4BNB054  
NONE  
NONE  
NONE  
NONE  
TDR  
TDR  
TDR & TXV  
TDR & TXV  
TDR & TXV  
TDR & TXV  
NONE  
10.80  
9.80  
FC4BNF036  
FC4BN(F,B)042  
FC4BNF038  
10.10  
9.80  
9.95  
10.65  
10.35  
10.35  
10.95  
11.40  
FG3AAA036  
11.00  
11.00  
FK4CNB006  
TDR & TXV  
TDR & TXV  
TDR & TXV  
TDR & TXV  
TDR & TXV  
FK4CNF001  
FK4CNF002  
FK4CNF003  
FK4CNF005  
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE  
CC5A/CD5AA042  
CE3AA042  
CK5A/CK5BA036  
34,600  
34,600  
35,000  
TDR  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
12.00  
12.00  
10.75  
10.75  
10.75  
036-E  
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE  
CC5A/CD5AA042  
CE3AA042  
CK5A/CK5BA042  
34,600  
34,600  
35,000  
TDR  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
12.00  
12.00  
10.75  
10.75  
10.75  
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AA042  
CE3AA042  
CK5A/CK5BA042  
34,600  
34,600  
35,000  
TDR  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
12.00  
12.00  
10.75  
10.75  
10.75  
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE  
CC5A/CD5AA042  
CE3AA042  
CK5A/CK5BA042  
34,600  
34,600  
35,000  
TDR  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
12.00  
12.00  
10.75  
10.75  
10.75  
COILS + 355MAV042040 VARIABLE SPEED FURNACE  
CC5A/CD5AA042  
CK5A/CK5BA042  
34,600  
35,000  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
10.75  
10.75  
COILS + 355MAV042060 VARIABLE SPEED FURNACE  
CC5A/CD5AA042  
CK5A/CK5BA042  
34,600  
34,600  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
10.75  
10.75  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CC5A/CD5AA042  
CK5A/CK5BA042  
34,600  
35,000  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
10.75  
10.75  
COILS + 355MAV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AA042  
CK5A/CK5BA042  
34,600  
34,600  
TDR  
TDR  
12.00  
12.00  
12.00  
12.00  
10.75  
10.75  
See notes on page 11.  
—9—  
COMBINATION RATINGS Continued  
SEER  
FACTORY  
SUPPLIED  
ENHANCE-  
MENT  
BRYANT GAS  
FURNACE OR  
STANDARD ACCESSORY ACCESSORY  
UNIT  
SIZE-SERIES  
INDOOR  
MODEL  
TOT. CAP.  
BTUH  
RATING  
TDR†  
TXV‡  
EERA  
CD5AA048*  
CC5A/CD5AA042  
CC5A/CD5AC048  
CC5A/CD5AW042  
CC5A/CD5AW048  
CE3AA042  
41,000  
41,000  
40,500  
40,500  
41,000  
41,000  
41,500  
41,500  
41,000  
41,000  
41,000  
41,000  
40,500  
41,000  
41,000  
41,500  
42,500  
41,000  
41,500  
41,000  
42,500  
41,000  
42,000  
NONE  
NONE  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.20  
11.50  
12.50  
11.20  
11.50  
11.00  
13.00  
12.00  
12.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.50  
11.20  
11.50  
10.25  
10.25  
10.15  
10.15  
10.25  
10.30  
10.35  
10.30  
10.25  
10.25  
10.25  
10.25  
10.15  
10.25  
10.10  
10.30  
10.95  
10.10  
10.30  
10.25  
11.65  
10.85  
11.30  
NONE  
NONE  
NONE  
NONE  
CE3AA048  
NONE  
CF5AA048  
NONE  
CK3BA042  
NONE  
CK3BA048  
NONE  
CK5A/CK5BA042  
CK5A/CK5BA048  
CK5A/CK5BW042  
CK5A/CK5BW048  
F(A,B)4AN(F,B,C)042  
F(A,B)4AN(F,B,C)048  
FC4BNB054  
NONE  
NONE  
NONE  
NONE  
TDR  
TDR  
TDR & TXV  
TDR & TXV  
TDR & TXV  
NONE  
FC4BN(F,B)042  
FC4BN(F,B)048  
FG3AAA048  
11.50  
11.50  
FK4CNB006  
TDR & TXV  
TDR & TXV  
TDR & TXV  
FK4CNF003  
042-E  
FK4CNF005  
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE  
CD5AA048  
CE3AA048  
CK5A/CK5BA048  
41,000  
41,000  
41,000  
TDR  
TDR  
TDR  
12.50  
12.50  
12.50  
12.50  
12.50  
12.50  
11.10  
11.05  
11.10  
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE  
CD5AA048  
CE3AA048  
CK5A/CK5BA048  
41,000  
41,000  
41,000  
TDR  
TDR  
TDR  
12.50  
12.50  
12.50  
12.50  
12.50  
12.50  
11.10  
11.05  
11.10  
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE  
CD5AA048  
CE3AA048  
CK5A/CK5BA048  
41,000  
41,000  
41,000  
TDR  
TDR  
TDR  
12.50  
12.50  
12.50  
12.50  
12.50  
12.50  
11.10  
11.05  
11.10  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CD5AA048  
CK5A/CK5BA048  
41,000  
41,000  
TDR  
TDR  
12.50  
12.00  
12.50  
12.00  
11.15  
11.15  
COILS + 355MAV060100 VARIABLE SPEED FURNACE  
CD5AA048  
CK5A/CK5BA048  
41,000  
41,000  
TDR  
TDR  
12.50  
12.50  
12.50  
12.50  
11.15  
11.15  
*CC5A/CD5AA060  
CC5A/CD5AC048  
CC5A/CD5AW048  
CC5A/CD5AW060  
CD5AA048  
46,800  
45,000  
46,000  
48,000  
46,500  
46,500  
48,000  
46,500  
46,500  
46,800  
46,500  
46,800  
45,000  
47,000  
46,500  
46,800  
46,500  
48,000  
46,500  
48,000  
48,000  
47,000  
48,000  
48,000  
48,000  
46,000  
47,500  
48,500  
48,000  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
NONE  
TDR  
10.60  
10.50  
10.50  
10.80  
10.50  
10.70  
11.00  
10.70  
10.50  
10.60  
10.50  
10.60  
10.50  
10.50  
10.50  
10.60  
10.50  
10.80  
11.00  
11.00  
11.50  
11.00  
11.00  
11.50  
11.00  
10.50  
10.70  
12.50  
12.20  
11.00  
10.80  
11.00  
11.20  
11.00  
11.00  
11.20  
11.10  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.20  
11.00  
10.80  
11.00  
11.20  
11.00  
11.00  
11.20  
11.10  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.20  
11.00  
11.00  
11.50  
9.65  
9.50  
9.60  
9.85  
9.60  
9.70  
9.95  
9.70  
9.65  
9.85  
9.65  
9.85  
9.65  
10.05  
9.65  
9.85  
9.65  
10.05  
9.60  
9.70  
10.00  
9.60  
9.70  
10.05  
10.00  
9.60  
9.80  
10.85  
10.55  
CE3AA048  
CE3AA060  
CF5AA048  
CK3BA048  
CK3BA060  
CK5A/CK5BA048  
CK5A/CK5BA060  
CK5A/CK5BN048  
CK5A/CK5BN060  
CK5A/CK5BT048  
CK5A/CK5BT060  
CK5A/CK5BW048  
CK5A/CK5BX060  
F(A,B)4AN(F,B,C)048  
F(A,B)4AN(F,B,C)060  
FB4ANB070  
TDR  
TDR  
048-E/F  
FC4BN(F,B)048  
FC4BN(F,B)060  
FC4BNB054  
TDR & TXV  
TDR & TXV  
TDR & TXV  
TDR & TXV  
NONE  
NONE  
TDR  
FC4BNB070  
FG3AAA048  
10.80  
11.00  
10.80  
11.00  
FG3AAA060  
FK4CNB006  
FK4CNF005  
TDR  
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE  
CC5A/CD5AC048  
CD5AA048  
45,000  
46,000  
46,000  
46,000  
TDR  
TDR  
TDR  
TDR  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
9.65  
9.75  
9.80  
9.80  
CK3BA048  
CK5A/CK5BA048  
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AA060  
CC5A/CD5AW048  
CC5A/CD5AW060  
CK3BA060  
CK5A/CK5BA060  
CK5A/CK5BW048  
CK5A/CK5BX060  
47,000  
46,000  
47,000  
47,000  
47,000  
46,000  
47,000  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
11.50  
11.20  
12.00  
11.50  
11.50  
11.20  
12.00  
11.50  
11.20  
12.00  
11.50  
11.50  
11.20  
12.00  
10.25  
10.10  
10.55  
10.45  
10.45  
10.20  
10.70  
See notes on page 11.  
—10—  
COMBINATION RATINGS Continued  
SEER  
FACTORY  
SUPPLIED  
ENHANCE-  
MENT  
BRYANT GAS  
FURNACE OR  
STANDARD ACCESSORY ACCESSORY  
UNIT  
SIZE-SERIES  
INDOOR  
MODEL  
TOT. CAP.  
BTUH  
RATING  
TDR†  
TXV‡  
EERA  
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE  
CC5A/CD5AA060  
CC5A/CD5AW048  
CC5A/CD5AW060  
CK3BA060  
CK5A/CK5BA060  
CK5A/CK5BW048  
CK5A/CK5BX060  
46,500  
46,000  
47,000  
46,500  
46,500  
46,000  
47,000  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
11.50  
11.20  
12.00  
11.50  
11.50  
11.20  
12.00  
11.50  
11.20  
12.00  
11.50  
11.50  
11.20  
12.00  
10.15  
10.05  
10.45  
10.35  
10.35  
10.10  
10.60  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CD5AA048  
CK3BA048  
CK5A/CK5BA048  
46,000  
46,000  
46,000  
TDR  
TDR  
TDR  
11.00  
11.00  
11.00  
11.00  
11.00  
11.00  
9.70  
9.75  
9.75  
COILS + 355MAV060080 VARIABLE SPEED FURNACE  
CC5A/CD5AA060  
CC5A/CD5AW060  
CD5AA048  
46,000  
47,000  
46,000  
46,000  
46,500  
47,000  
46,000  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
11.00  
11.20  
11.00  
11.00  
11.00  
11.20  
11.00  
11.00  
11.20  
11.00  
11.00  
11.00  
11.20  
11.00  
9.70  
9.95  
9.60  
9.70  
9.90  
10.15  
9.70  
CK3BA048  
CK5A/CK5BA060  
CK5A/CK5BX060  
CK5A/CK5BA048  
048-E/F  
COILS + 355MAV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AA060  
CC5A/CD5AC048  
CC5A/CD5AW060  
CD5AA048  
46,000  
45,000  
47,000  
46,000  
46,000  
46,500  
46,000  
46,000  
47,000  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
11.20  
11.00  
11.80  
11.00  
11.00  
11.20  
11.00  
11.20  
11.80  
11.20  
11.00  
11.80  
11.00  
11.00  
11.20  
11.00  
11.20  
11.80  
9.95  
9.70  
10.20  
9.90  
CK3BA048  
9.95  
CK3BA060  
10.15  
9.95  
CK5A/CK5BA048  
CK5A/CK5BA060  
CK5A/CK5BX060  
10.40  
10.40  
COILS + 355MAV060120 VARIABLE SPEED FURNACE  
CC5A/CD5AA060  
CC5A/CD5AW048  
CC5A/CD5AW060  
CK3BA060  
CK5A/CK5BA060  
CK5A/CK5BW048  
CK5A/CK5BX060  
46,000  
46,000  
47,000  
46,500  
46,000  
46,000  
47,000  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
TDR  
11.20  
11.20  
11.80  
11.20  
11.20  
11.20  
11.80  
11.20  
11.20  
11.80  
11.20  
11.20  
11.20  
11.80  
9.95  
9.90  
10.25  
10.20  
10.20  
9.95  
10.45  
CC5A/CD5AW060*  
CC5A/CD5AA060  
CE3AA060  
56,500  
54,500  
56,500  
54,500  
56,500  
57,000  
57,500  
57,500  
57,000  
56,000  
57,500  
NONE  
NONE  
10.80  
10.60  
10.80  
10.60  
10.80  
10.80  
11.00  
11.00  
10.80  
10.80  
12.00  
11.00  
10.80  
11.00  
10.80  
11.00  
11.00  
10.80  
11.00  
10.80  
11.00  
10.80  
11.00  
9.70  
9.55  
9.80  
9.55  
9.70  
9.40  
9.80  
9.80  
9.40  
9.65  
10.30  
NONE  
CK5A/CK5BA060  
CK5A/CK5BX060  
F(A,B)4AN(F,B,C)060  
FB4ANB070  
NONE  
NONE  
TDR  
TDR  
060-E  
FC4BNB070  
TDR & TXV  
TDR & TXV  
NONE  
11.00  
FC4BN(F,B)060  
FG3AAA060  
11.00  
FK4CNB006  
TDR & TXV  
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AW060  
CK5A/CK5BW060  
56,500  
56,500  
TDR  
TDR  
11.80  
11.80  
11.80  
11.80  
10.30  
10.30  
* Tested Combination  
† In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use  
either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. All Bryant furnaces are equipped with TDR except for the 394HAD.  
‡ Based on computer simulation. TXV must be hard shutoff type.  
NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.  
2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other  
combinations are determined under DOE computer simulation procedures.  
3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.  
4. Minimum outdoor operating ambient in cooling mode is 55°F (12.8°C), maximum 125°F (51.7°C).  
—11—  
DETAILED COOLING CAPACITIES*  
CONDENSER ENTERING AIR TEMPERATURES °F  
EVAPORATOR  
AIR  
85  
Capacity  
95  
Capacity  
105  
Capacity  
115  
Capacity  
125  
Capacity  
Total  
Total  
System  
Total  
Total  
System  
Total  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
System  
System  
System  
CFM  
EWB  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
594D018-E Outdoor Section With CK5A/CK5BA024 Indoor Section  
72  
67  
62  
57  
19.6  
18.0  
16.5  
15.9  
9.74  
12.4  
14.9  
15.9  
1.48  
1.46  
1.44  
1.43  
18.9  
17.3  
15.9  
15.4  
9.46  
12.1  
14.6  
15.4  
1.66  
1.63  
1.61  
1.60  
18.1  
16.6  
15.2  
14.8  
9.17  
11.8  
14.3  
14.8  
1.85  
1.82  
1.80  
1.79  
17.4  
15.9  
14.5  
14.2  
8.90  
11.5  
13.9  
14.2  
2.00  
2.00  
2.00  
2.00  
16.6  
15.1  
13.8  
13.6  
8.60  
11.2  
13.5  
13.6  
2.33  
2.28  
2.25  
2.26  
525  
600  
675  
72  
67  
62  
57  
19.9  
18.3  
16.8  
16.4  
10.1  
13.1  
15.9  
16.4  
1.51  
1.49  
1.46  
1.46  
19.2  
17.6  
16.2  
15.9  
9.86  
12.8  
15.6  
15.9  
1.69  
1.66  
1.65  
1.64  
18.4  
16.9  
15.5  
15.3  
9.57  
12.5  
15.2  
15.3  
1.88  
1.86  
1.84  
1.83  
17.6  
16.1  
14.8  
14.7  
9.30  
12.2  
14.7  
14.7  
2.10  
2.00  
2.00  
2.00  
16.7  
15.3  
14.1  
14.1  
9.01  
11.9  
14.1  
14.1  
2.36  
2.30  
2.28  
2.29  
72  
67  
62  
57  
20.1  
18.6  
17.1  
16.9  
10.5  
13.8  
16.7  
16.9  
1.54  
1.52  
1.51  
1.49  
19.3  
17.9  
16.4  
16.4  
10.2  
13.5  
16.3  
16.4  
1.72  
1.70  
1.68  
1.68  
18.6  
17.1  
15.8  
15.8  
9.98  
13.2  
15.8  
15.8  
1.92  
1.89  
1.87  
1.87  
17.7  
16.3  
15.1  
15.1  
9.68  
12.9  
15.1  
15.1  
2.10  
2.10  
2.00  
2.00  
16.9  
15.4  
14.4  
14.5  
9.38  
12.6  
14.4  
14.5  
2.38  
2.33  
2.31  
2.32  
Multipliers for Determining the Performance With Other Indoor Sections  
Cooling  
Cooling  
Indoor  
Indoor  
Section  
Size  
Capacity  
0.98  
1.00  
1.00  
1.00  
1.00  
0.98  
1.00  
1.00  
0.95  
1.00  
1.00  
0.97  
1.00  
0.97  
Power  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
0.98  
0.99  
1.01  
0.96  
1.00  
1.00  
Section  
Size  
001  
002  
Capacity  
1.02  
Power  
CC5A/CD5AA  
018  
024  
024  
024  
024  
018  
024  
024  
018  
024  
024  
018  
024  
024  
FK4CNF  
0.91  
0.91  
1.02  
CC5A/CD5AW  
CE3AA  
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
018  
024  
018  
024  
0.97  
1.00  
0.97  
1.00  
0.90  
0.90  
0.90  
0.90  
CK3BA  
CK5A/CK5BA  
CK5A/CK5BA  
CK5A/CK5BW  
F(A,B)4AN(F,C)  
COILS + 355MAV042060 VARIABLE SPEED FURNACE  
CC5A/CD5AW  
CK5A/CK5BW  
024  
024  
1.00  
1.00  
0.93  
0.93  
FC4BNF  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
FF1(B,C,D)NA  
CC5A/CD5AW  
CK5A/CK5AW  
024  
024  
1.00  
1.00  
0.92  
0.92  
FG3AAA  
See notes on page 18.  
—12—  
DETAILED COOLING CAPACITIES* Continued  
CONDENSER ENTERING AIR TEMPERATURES °F  
EVAPORATOR  
AIR  
85  
Capacity  
95  
Capacity  
105  
Capacity  
115  
Capacity  
125  
Capacity  
Total  
Total  
System  
Total  
Total  
System  
Total  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
System  
System  
System  
CFM  
EWB  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
594D024-E Outdoor Section With CC5A/CD5AA030 Indoor Section  
72  
67  
62  
57  
25.7  
23.6  
21.6  
20.8  
12.8  
16.3  
19.7  
20.8  
2.11  
2.08  
2.06  
2.05  
24.7  
22.7  
20.8  
20.1  
12.4  
15.9  
19.3  
20.1  
2.34  
2.30  
2.27  
2.25  
23.7  
21.8  
19.9  
19.4  
12.1  
15.5  
18.8  
19.4  
2.59  
2.55  
2.52  
2.49  
22.7  
20.8  
19.0  
18.7  
11.7  
15.2  
18.4  
18.7  
2.8  
2.8  
2.7  
2.7  
21.6  
19.8  
18.1  
17.9  
11.3  
14.8  
17.8  
17.9  
3.17  
3.13  
3.10  
3.07  
700  
800  
900  
72  
67  
62  
57  
26.0  
23.9  
22.0  
21.5  
13.3  
17.3  
20.9  
21.5  
2.15  
2.13  
2.10  
2.09  
25.0  
23.0  
21.1  
20.8  
12.9  
16.9  
20.4  
20.8  
2.38  
2.35  
2.32  
2.31  
24.0  
22.0  
20.2  
20.1  
12.6  
16.5  
19.9  
20.1  
2.63  
2.59  
2.56  
2.56  
22.9  
21.0  
19.3  
19.3  
12.2  
16.1  
19.3  
19.3  
2.9  
2.8  
2.8  
2.8  
21.8  
20.0  
18.5  
18.5  
11.8  
15.7  
18.5  
18.5  
3.21  
3.17  
3.14  
3.14  
72  
67  
62  
57  
26.3  
24.2  
22.3  
22.1  
13.8  
18.2  
22.0  
22.1  
2.19  
2.17  
2.14  
2.14  
25.3  
23.2  
21.4  
21.5  
13.5  
17.8  
21.4  
21.5  
2.42  
2.39  
2.36  
2.37  
24.2  
22.2  
20.6  
20.6  
13.1  
17.4  
20.6  
20.6  
2.67  
2.63  
2.60  
2.60  
23.1  
21.2  
19.8  
19.8  
12.7  
17.0  
19.8  
19.8  
2.9  
2.9  
2.8  
2.8  
21.9  
20.1  
19.0  
19.0  
12.3  
16.6  
19.0  
19.0  
3.25  
3.21  
3.18  
3.18  
Multipliers for Determining the Performance With Other Indoor Sections  
Cooling  
Cooling  
Indoor  
Indoor  
Section  
Size  
Capacity  
1.00  
1.00  
1.00  
1.01  
1.00  
1.01  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.02  
1.00  
1.02  
1.00  
1.02  
Power  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
0.99  
1.00  
0.99  
1.01  
1.01  
Section  
FG3AAA  
FK4CNF  
Size  
024  
001  
002  
003  
Capacity  
0.98  
Power  
CC5A/CD5AA  
CC5A/CD5AW  
CE3AA  
024  
030  
024  
030  
024  
030  
024  
024  
024  
030  
024  
030  
024  
024  
030  
024  
030  
024  
030  
1.00  
0.94  
0.94  
0.91  
1.04  
1.05  
1.06  
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CE3AA  
030  
030  
030  
1.01  
1.01  
1.01  
0.92  
0.92  
0.92  
CF5AA  
CG5AA  
CK3BA  
CK5A/CK5BA  
COILS + 355MAV042040 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CK5A/CK5BA  
030  
030  
1.01  
1.01  
0.94  
0.94  
CK5A/CK5BA  
COILS + 355MAV042060 VARIABLE SPEED FURNACE  
CK5A/CK5BW  
F(A,B)4AN(F,C)  
CC5A/CD5AA  
CK5A/CK5BA  
030  
030  
1.01  
1.01  
0.94  
0.94  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
FC4BNF  
CC5A/CD5AA  
CK5A/CK5BA  
030  
030  
1.01  
1.01  
0.94  
0.94  
FF1(B,C,D)NA  
See notes on page 18.  
—13—  
DETAILED COOLING CAPACITIES* Continued  
CONDENSER ENTERING AIR TEMPERATURES °F  
EVAPORATOR  
AIR  
85  
Capacity  
95  
Capacity  
105  
Capacity  
115  
Capacity  
125  
Capacity  
Total  
Total  
System  
Total  
Total  
System  
Total  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
System  
System  
System  
CFM  
EWB  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
594D030-E Outdoor Section With CC5A/CD5AA036 Indoor Section  
72  
67  
62  
57  
32.5  
29.7  
27.1  
26.1  
16.1  
20.4  
24.5  
26.1  
2.58  
2.59  
2.62  
2.64  
31.2  
28.5  
26.0  
25.1  
15.6  
19.9  
24.0  
25.1  
2.97  
2.99  
3.01  
3.04  
29.8  
27.2  
24.8  
24.1  
15.1  
19.3  
23.3  
24.1  
3.42  
3.43  
3.46  
3.47  
28.3  
25.7  
23.4  
23.0  
14.5  
18.7  
22.6  
23.0  
3.9  
3.9  
4.0  
4.0  
26.3  
23.6  
21.4  
21.4  
13.8  
17.9  
21.4  
21.4  
5.04  
5.11  
5.01  
5.03  
875  
1000  
1125  
72  
67  
62  
57  
33.0  
30.2  
27.7  
27.0  
16.8  
21.6  
26.1  
27.0  
2.61  
2.62  
2.64  
2.66  
31.7  
29.0  
26.5  
26.1  
16.3  
21.1  
25.5  
26.1  
3.00  
3.02  
3.04  
3.06  
30.2  
27.6  
25.3  
25.0  
15.8  
20.6  
24.8  
25.0  
3.44  
3.46  
3.48  
3.50  
28.7  
26.1  
23.9  
23.8  
15.2  
20.0  
23.8  
23.8  
4.0  
4.0  
4.1  
4.0  
26.7  
24.0  
22.1  
22.2  
14.5  
19.1  
22.1  
22.2  
5.04  
5.12  
5.12  
5.07  
72  
67  
62  
57  
33.4  
30.6  
28.2  
27.9  
17.4  
22.8  
27.6  
27.9  
2.64  
2.66  
2.67  
2.68  
32.0  
29.4  
27.0  
26.9  
17.0  
22.3  
26.8  
26.9  
3.03  
3.05  
3.07  
3.08  
30.6  
28.0  
25.8  
25.8  
16.5  
21.7  
25.8  
25.8  
3.52  
3.54  
3.56  
3.58  
29.0  
26.4  
24.5  
24.6  
15.9  
21.1  
24.5  
24.6  
4.0  
4.1  
4.1  
4.1  
27.0  
24.3  
22.6  
22.8  
15.2  
20.3  
22.6  
22.8  
5.07  
5.15  
5.34  
5.18  
Multipliers for Determining the Performance With Other Indoor Sections  
Cooling  
Cooling  
Indoor  
Indoor  
Section  
Size  
Capacity  
0.97  
1.00  
0.97  
1.00  
0.98  
0.99  
1.00  
0.97  
1.00  
0.97  
1.00  
0.97  
1.00  
0.97  
0.99  
0.97  
0.99  
0.98  
0.99  
Power  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
0.99  
1.01  
0.99  
1.01  
1.00  
1.00  
Section  
Size  
001  
002  
003  
Capacity  
1.01  
Power  
CC5A/CD5AA  
030  
036  
030  
036  
030  
036  
036  
030  
036  
030  
036  
030  
036  
030  
036  
030  
036  
030  
036  
FK4CNF  
0.96  
0.96  
0.92  
1.01  
CC5A/CD5AW  
CD5AW  
1.02  
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE  
CE3AA  
CC5A/CD5AA  
CE3AA  
036  
036  
036  
1.01  
1.00  
1.01  
0.92  
0.93  
0.93  
CF5AA  
CK3BA  
CK5A/CK5BA  
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CE3AA  
036  
036  
036  
1.01  
1.00  
1.01  
0.92  
0.93  
0.92  
CK5A/CK5BA  
CK5A/CK5BW  
F(A,B)4AN(F,C)  
FC4BNF  
CK5A/CK5BA  
COILS + 355MAV042040 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CK5A/CK5BA  
036  
036  
1.01  
1.01  
0.94  
0.94  
COILS + 355MAV042060 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CK5A/CK5BA  
036  
036  
1.01  
1.01  
0.94  
0.96  
FF1(B,C,D)NA  
FG3AAA  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CK5A/CK5BA  
036  
036  
1.01  
1.01  
0.94  
0.94  
See notes on page 18.  
—14—  
DETAILED COOLING CAPACITIES* Continued  
CONDENSER ENTERING AIR TEMPERATURES °F  
EVAPORATOR  
AIR  
85  
Capacity  
95  
Capacity  
105  
Capacity  
115  
Capacity  
125  
Capacity  
Total  
Total  
System  
Total  
Total  
System  
Total  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
System  
System  
System  
CFM  
EWB  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
594D036-E Outdoor Section With CC5A/CD5AA042 Indoor Section  
72  
67  
62  
57  
39.1  
35.9  
32.9  
31.6  
19.4  
24.7  
29.8  
31.6  
3.13  
3.10  
3.08  
3.08  
37.5  
34.5  
31.6  
30.6  
18.8  
24.1  
29.2  
30.6  
3.47  
3.44  
3.42  
3.41  
35.9  
33.0  
30.2  
29.5  
18.3  
23.5  
28.5  
29.5  
3.84  
3.81  
3.79  
3.78  
34.3  
31.4  
28.8  
28.4  
17.7  
22.9  
27.7  
28.4  
4.2  
4.2  
4.1  
4.1  
32.6  
29.8  
27.3  
27.1  
17.7  
22.2  
26.9  
27.1  
4.69  
4.64  
4.61  
4.57  
1050  
1200  
1350  
72  
67  
62  
57  
39.6  
36.5  
33.5  
32.8  
20.2  
26.2  
31.8  
32.8  
3.19  
3.16  
3.14  
3.14  
38.1  
35.0  
32.2  
31.7  
19.7  
25.6  
31.0  
31.7  
3.53  
3.50  
3.48  
3.48  
36.4  
33.5  
30.8  
30.5  
19.1  
25.0  
30.2  
30.5  
3.91  
3.87  
3.84  
3.85  
34.7  
31.8  
29.4  
29.3  
18.5  
24.4  
29.3  
29.3  
4.3  
4.2  
4.2  
4.2  
32.9  
30.2  
28.0  
27.9  
17.9  
23.7  
28.0  
27.9  
4.75  
4.70  
4.66  
4.64  
72  
67  
62  
57  
40.0  
36.9  
34.0  
33.7  
21.0  
27.6  
33.4  
33.7  
3.25  
3.22  
3.20  
3.20  
38.4  
35.3  
32.7  
32.6  
20.5  
27.0  
32.5  
32.6  
3.59  
3.56  
3.53  
3.54  
36.7  
33.8  
31.3  
31.3  
19.9  
26.4  
31.3  
31.3  
3.96  
3.93  
3.90  
3.91  
34.9  
32.1  
30.1  
30.1  
19.3  
25.8  
30.1  
30.1  
4.3  
4.3  
4.3  
4.3  
33.1  
30.4  
28.7  
28.6  
18.6  
25.1  
28.7  
28.6  
4.80  
4.76  
4.73  
4.71  
Multipliers for Determining the Performance With Other Indoor Sections  
Cooling  
Cooling  
Indoor  
Indoor  
Section  
CE3AA  
Section  
Size  
Capacity  
1.00  
1.00  
0.99  
1.00  
0.98  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
0.99  
0.98  
1.00  
1.00  
1.05  
0.98  
0.98  
1.03  
0.99  
0.99  
1.00  
1.03  
Power  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.02  
1.01  
1.01  
1.00  
1.02  
1.00  
0.93  
0.98  
0.98  
0.93  
0.94  
Size  
042  
042  
Capacity  
0.99  
Power  
CC5A/CD5AA  
036  
042  
042  
036  
036  
042  
036  
036  
036  
042  
036  
042  
036  
042  
036  
042  
042  
054  
036  
036  
006  
001  
002  
003  
005  
0.95  
0.94  
CK5A/CK5BA  
0.99  
CC5A/CD5AW  
CD5AW  
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CE3AA  
042  
042  
042  
0.99  
0.99  
0.99  
0.94  
0.95  
0.94  
CE3AA  
CK5A/CK5BA  
CF5AA  
CG5AA  
CK3BA  
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CE3AA  
042  
042  
042  
0.99  
0.99  
0.99  
0.94  
0.95  
0.94  
CK5A/CK5BA  
CK5A/CK5BA  
CK5A/CK5BW  
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CE3AA  
042  
042  
042  
0.99  
0.99  
0.99  
0.94  
0.95  
0.94  
CK5A/CK5BA  
F(A,B)4AN(F,C)  
F(A,B)4AN(F,B,C)  
FC4BN(F,B)  
FC4BNB  
COILS + 355MAV042040 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CK5A/CK5BA  
042  
042  
0.99  
0.99  
0.93  
0.93  
COILS + 355MAV042060 VARIABLE SPEED FURNACE  
FC4BNF  
CC5A/CD5AA  
CK5A/CK5BA  
042  
042  
0.99  
0.99  
0.93  
0.93  
FG3AAA  
FK4CNB  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
FK4CNF  
CC5A/CD5AA  
CK5A/CK5BA  
042  
042  
0.99  
0.99  
0.93  
0.93  
COILS + 355MAV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CK5A/CK5BA  
042  
042  
0.99  
0.99  
0.93  
0.93  
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
042  
0.99  
0.94  
See notes on page 18.  
—15—  
DETAILED COOLING CAPACITIES* Continued  
CONDENSER ENTERING AIR TEMPERATURES °F  
EVAPORATOR  
AIR  
85  
Capacity  
95  
Capacity  
105  
Capacity  
115  
Capacity  
125  
Capacity  
Total  
Total  
System  
Total  
Total  
System  
Total  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
System  
System  
System  
CFM  
EWB  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
594D042-E Outdoor Section With CC5A/CD5AA048 Indoor Section  
72  
67  
62  
57  
45.8  
42.0  
38.4  
36.6  
22.5  
28.4  
34.2  
36.6  
3.61  
3.57  
3.54  
3.53  
44.0  
40.4  
36.9  
35.4  
21.9  
27.8  
33.5  
35.4  
3.99  
3.95  
3.91  
3.91  
42.3  
38.7  
35.4  
34.2  
21.2  
27.1  
32.7  
34.2  
4.42‘  
4.38  
4.34  
4.33  
40.4  
37.1  
33.8  
33.0  
20.5  
26.4  
32.0  
33.0  
4.9  
4.8  
4.8  
4.8  
38.5  
35.3  
32.3  
31.8  
19.8  
25.7  
31.1  
31.8  
5.44  
5.40  
5.36  
5.36  
1225  
1400  
1575  
72  
67  
62  
57  
46.5  
42.7  
39.1  
37.9  
23.4  
30.0  
36.4  
37.9  
3.68  
3.64  
3.61  
3.60  
44.7  
41.0  
37.5  
36.6  
22.7  
29.3  
35.5  
36.6  
4.06  
4.02  
3.98  
3.98  
42.8  
39.3  
35.9  
35.4  
22.1  
28.7  
34.7  
35.4  
4.49  
4.45  
4.41  
4.41  
40.9  
37.5  
34.4  
34.1  
21.4  
27.9  
33.8  
34.1  
4.9  
4.9  
4.8  
4.8  
38.9  
35.7  
32.8  
32.7  
20.7  
27.2  
32.7  
32.7  
5.51  
5.46  
5.42  
5.43  
72  
67  
62  
57  
47.0  
43.2  
39.6  
39.0  
24.3  
31.6  
38.3  
39.0  
3.75  
3.71  
3.68  
3.67  
45.1  
41.5  
38.1  
37.7  
23.6  
30.9  
38.3  
37.7  
4.13  
4.09  
4.05  
4.05  
43.2  
39.7  
36.5  
36.4  
22.9  
30.2  
36.3  
36.4  
4.56  
4.51  
4.48  
4.48  
41.3  
37.9  
35.0  
35.0  
22.2  
29.5  
35.0  
35.0  
5.0  
4.9  
4.9  
4.9  
39.2  
36.1  
33.6  
33.6  
21.5  
28.8  
33.6  
33.6  
5.57  
5.53  
5.49  
5.50  
Multipliers for Determining the Performance With Other Indoor Sections  
Cooling  
Cooling  
Indoor  
Indoor  
Section  
Size  
Capacity  
1.00  
0.99  
0.99  
1.00  
1.00  
1.00  
1.01  
1.01  
1.00  
1.00  
1.00  
1.00  
0.99  
1.00  
1.00  
1.01  
1.00  
1.01  
1.04  
1.00  
1.04  
Power  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.01  
1.02  
1.01  
1.02  
1.00  
1.00  
0.94  
Section  
Size  
003  
005  
Capacity  
1.00  
Power  
CC5A/CD5AA  
CC5A/CD5AC  
CC5A/CD5AW  
042  
048  
042  
048  
048  
042  
048  
048  
042  
048  
042  
048  
042  
048  
042  
048  
042  
048  
054  
048  
006  
FK4CNF  
0.95  
0.96  
1.02  
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE  
CD5AA  
CE3AA  
048  
048  
048  
1.00  
1.00  
1.00  
0.93  
0.94  
0.93  
CD5AA  
CE3AA  
CK5A/CK5BA  
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE  
CF5AA  
CK3BA  
CD5AA  
CE3AA  
048  
048  
048  
1.00  
1.00  
1.00  
0.93  
0.94  
0.93  
CK5A/CK5BA  
CK5A/CK5BA  
CK5A/CK5BW  
F(A,B)4AN(F,B,C)  
FC4BN(F,B)  
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE  
CD5AA  
CE3AA  
048  
048  
048  
1.00  
1.00  
1.00  
0.93  
0.94  
0.93  
CK5A/CK5BA  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CD5A/CD5BA  
CK5A/CK5BA  
048  
048  
1.00  
1.00  
0.92  
0.92  
COILS + 355MAV060100 VARIABLE SPEED FURNACE  
FC4BNB  
FG3AAA  
FK4CNB  
CD5AA  
048  
048  
1.00  
1.00  
0.92  
0.92  
CK5A/CK5BA  
See notes on page 18.  
—16—  
DETAILED COOLING CAPACITIES* Continued  
CONDENSER ENTERING AIR TEMPERATURES °F  
EVAPORATOR  
AIR  
85  
Capacity  
95  
Capacity  
105  
Capacity  
115  
Capacity  
125  
Capacity  
Total  
Total  
System  
Total  
Total  
System  
Total  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
System  
System  
System  
CFM  
EWB  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
594D048-E, F Outdoor Section With CC5A/CD5AA060 Indoor Section  
72  
67  
62  
57  
52.3  
48.3  
44.4  
42.0  
25.6  
32.5  
39.2  
42.0  
4.37  
4.35  
4.34  
4.29  
50.2  
46.3  
42.5  
40.5  
24.8  
31.7  
38.3  
40.5  
4.90  
4.87  
4.86  
4.81  
47.9  
44.2  
40.6  
39.0  
24.0  
30.8  
37.3  
39.0  
5.48  
5.45  
5.43  
5.38  
45.6  
42.1  
38.5  
37.4  
23.1  
29.9  
36.2  
37.4  
6.11  
6.08  
6.05  
5.99  
43.1  
39.8  
36.5  
35.7  
22.2  
29.0  
35.1  
35.7  
6.78  
6.73  
6.70  
6.64  
1500  
1700  
1800  
72  
67  
62  
57  
53.1  
49.1  
45.1  
43.4  
26.6  
34.2  
41.5  
43.4  
4.45  
4.42  
4.41  
4.37  
50.8  
47.0  
43.2  
41.8  
25.8  
33.4  
40.5  
41.8  
4.97  
4.95  
4.93  
4.89  
48.5  
44.8  
41.2  
40.2  
24.9  
32.5  
39.4  
40.2  
5.55  
5.52  
5.50  
5.46  
46.1  
42.5  
39.1  
38.5  
24.1  
31.6  
38.2  
38.5  
6.19  
6.15  
6.12  
6.08  
43.5  
40.2  
37.1  
36.8  
23.1  
30.6  
36.8  
36.8  
6.86  
6.81  
6.78  
6.73  
72  
67  
62  
57  
53.4  
49.3  
45.4  
44.0  
27.0  
35.0  
42.5  
44.0  
4.49  
4.46  
4.44  
4.41  
51.1  
47.3  
43.5  
42.4  
26.2  
34.2  
41.5  
42.4  
5.01  
4.98  
4.97  
4.93  
48.7  
45.1  
41.5  
40.8  
25.4  
33.3  
40.3  
40.8  
5.59  
5.56  
5.54  
5.50  
46.3  
42.8  
39.4  
39.1  
24.5  
32.4  
39.0  
39.1  
6.22  
6.19  
6.16  
6.12  
43.7  
40.4  
37.4  
37.3  
23.6  
31.4  
37.4  
37.3  
6.90  
6.85  
6.82  
6.78  
Multipliers for Determining the Performance With Other Indoor Sections  
Cooling  
Cooling  
Indoor  
Section  
Indoor  
Section  
Size  
Capacity  
1.00  
0.96  
0.98  
1.03  
0.99  
0.99  
1.03  
0.99  
0.99  
1.00  
0.99  
1.00  
0.96  
1.00  
0.99  
1.00  
0.99  
1.03  
0.99  
1.03  
1.03  
1.00  
1.03  
1.03  
0.98  
1.01  
1.04  
1.03  
Power  
1.00  
0.99  
1.00  
1.00  
1.00  
1.00  
1.00  
0.99  
1.00  
1.00  
1.00  
1.00  
0.98  
1.00  
1.00  
1.00  
1.00  
1.00  
1.02  
1.03  
1.02  
1.02  
1.03  
1.02  
1.00  
1.00  
0.94  
0.95  
Size  
Capacity  
Power  
0.94  
CC5A/CD5AA  
CC5A/CD5AC  
CC5A/CD5AW  
060  
048  
048  
060  
048  
048  
060  
048  
048  
060  
048  
060  
048  
060  
048  
060  
048  
060  
048  
060  
070  
048  
060  
070  
048  
060  
006  
005  
CK5A/CK5BX  
060  
1.00  
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CC5A/CD5AW  
060  
048  
060  
060  
060  
048  
060  
0.99  
0.98  
1.00  
0.99  
0.99  
0.98  
1.00  
0.95  
0.95  
0.95  
0.95  
0.95  
0.95  
0.95  
CD5AA  
CE3AA  
CK3BA  
CK5A/CK5BA  
CK5A/CK5BW  
CK5A/CK5BX  
CF5AA  
CK3BA  
COILS + 355MAV042080 VARIABLE SPEED FURNACE  
CK5A/CK5BA  
CK5A/CK5BN  
CK5A/CK5BT  
CD5AA  
CK3BA  
048  
048  
048  
0.98  
0.98  
0.98  
0.97  
0.97  
0.97  
CK5A/CK5BA  
COILS + 355MAV060080 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CC5A/CD5AW  
CD5AA  
060  
060  
048  
048  
060  
060  
048  
0.98  
1.00  
0.98  
0.98  
0.99  
1.00  
0.98  
0.98  
0.98  
0.98  
0.98  
0.98  
0.98  
0.98  
CK5A/CK5BW  
CK5A/CK5BX  
CK3BA  
F(A,B)4AN(F,B,C)  
CK5A/CK5BA  
CK5A/CK5BX  
CK5ACK5BA  
FB4ANB  
FC4BN(F,B)  
COILS + 355MAV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CC5A/CD5AC  
CC5A/CD5AW  
CD5AA  
060  
048  
060  
048  
048  
060  
048  
060  
060  
0.98  
0.96  
1.00  
0.98  
0.98  
0.99  
0.98  
0.98  
1.00  
0.96  
0.97  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
FC4BNB  
FG3AAA  
FK4CNB  
FK4CNF  
CK3BA  
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE  
CK5A/CK5BA  
CK5A/CK5BA  
CK5A/CK5BX  
CC5A/CD5AC  
CD5AA  
048  
048  
048  
048  
0.96  
0.98  
0.98  
0.98  
0.97  
0.97  
0.97  
0.97  
CK3BA  
COILS + 355MAV060120 VARIABLE SPEED FURNACE  
CK5A/CK5BA  
CC5A/CD5AA  
CC5A/CD5AW  
060  
048  
060  
060  
060  
048  
060  
0.98  
0.98  
1.00  
0.99  
0.98  
0.98  
1.00  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE  
CC5A/CD5AA  
CC5A/CD5AW  
060  
048  
060  
060  
060  
048  
1.00  
0.98  
1.00  
1.00  
1.00  
0.98  
0.94  
0.94  
0.94  
0.94  
0.94  
0.94  
CK3BA  
CK5A/CK5BA  
CK5A/CK5BW  
CK5A/CK5BX  
CK3BA  
CK5A/CK5BA  
CK5A/CK5BW  
See notes on page 18.  
—17—  
DETAILED COOLING CAPACITIES* Continued  
CONDENSER ENTERING AIR TEMPERATURES °F  
EVAPORATOR  
AIR  
85  
Capacity  
95  
Capacity  
105  
Capacity  
115  
Capacity  
125  
Capacity  
Total  
Total  
System  
Total  
Total  
System  
Total  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
MBtuh†  
System  
System  
System  
CFM  
EWB  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
Total Sens‡ Kw**  
594D060-E Outdoor Section With CC5A/CD5AW060 Indoor Section  
72  
67  
62  
57  
63.4  
57.8  
52.4  
50.2  
31.4  
39.6  
47.6  
50.2  
5.42  
5.36  
5.28  
5.20  
61.0  
55.4  
49.9  
48.2  
30.4  
38.6  
46.4  
48.2  
5.88  
5.79  
5.68  
5.59  
58.2  
52.5  
46.9  
45.9  
29.4  
37.5  
44.8  
45.9  
6.35  
6.21  
6.02  
5.93  
54.9  
49.0  
43.4  
43.2  
28.2  
36.1  
42.8  
43.2  
6.7  
6.5  
6.2  
6.2  
50.9  
44.8  
39.7  
40.1  
26.8  
34.4  
39.7  
40.1  
7.13  
6.76  
6.37  
6.37  
1750  
2000  
2250  
72  
67  
62  
57  
64.7  
59.0  
53.6  
52.2  
32.8  
42.0  
50.7  
52.2  
5.44  
5.38  
5.31  
5.24  
62.1  
56.5  
51.1  
50.3  
31.8  
41.0  
49.4  
50.3  
5.91  
5.82  
5.72  
5.65  
59.3  
53.6  
48.3  
48.0  
30.8  
39.9  
47.6  
48.0  
6.38  
6.26  
6.10  
6.03  
56.0  
50.2  
45.1  
45.4  
29.7  
38.5  
45.1  
45.4  
6.8  
6.6  
6.3  
6.3  
52.1  
46.1  
41.9  
42.3  
28.3  
37.0  
41.9  
42.3  
7.22  
6.89  
6.59  
6.57  
72  
67  
62  
57  
65.7  
60.0  
54.6  
54.0  
34.1  
44.4  
53.4  
54.0  
5.34  
5.28  
5.34  
5.27  
62.9  
57.4  
52.2  
52.0  
33.1  
43.3  
51.8  
52.0  
5.93  
5.86  
5.77  
5.69  
60.1  
54.5  
49.6  
49.8  
32.1  
42.2  
49.6  
49.8  
6.42  
6.30  
6.17  
6.10  
56.9  
51.2  
46.9  
47.2  
31.0  
40.9  
46.9  
47.2  
6.8  
6.7  
6.5  
6.4  
53.0  
47.0  
43.7  
44.0  
29.7  
39.3  
43.7  
44.0  
7.30  
7.00  
6.76  
6.74  
Multipliers for Determining the Performance With Other Indoor Sections  
Cooling  
Cooling  
Indoor  
Indoor  
Section  
Size  
Capacity  
0.96  
Power  
0.98  
1.00  
1.00  
0.98  
1.00  
1.04  
1.02  
Section  
FC4BNB  
FC4BN(F,B)  
FG3AAA  
FK4CNB  
Size  
070  
060  
060  
006  
Capacity  
1.02  
Power  
CC5A/CD5AA  
CC5A/CD5AW  
CE3AA  
060  
060  
060  
060  
060  
060  
070  
1.02  
1.04  
1.00  
0.97  
1.00  
1.01  
1.00  
0.99  
CK5A/CK5BA  
CK5A/CK5BX  
F(A,B)4AN(F,B,C)  
FB4ANB  
0.96  
1.02  
1.00  
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE  
1.01  
CC5A/CD5AW  
CK5A/CK5BW  
060  
060  
1.00  
1.00  
0.94  
0.94  
1.02  
*
Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI Standard 210/240-94.If additional tubing length and/or indoor  
unit is located above outdoor unit, a slight variation in capacity may occur.  
Total and sensible capacities are net capacities. Blower motor heat has been subtracted.  
Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh  
(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air  
per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed.  
** Unit kw is total of indoor and outdoor unit kilowatts.  
—18—  
CONDENSER ONLY RATINGS*  
CONDENSER ENTERING AIR TEMPERATURES °F  
SST  
°F  
55  
65  
75  
85  
95  
105  
115  
594D018-E  
16.9  
77.1  
16.2  
86.9  
15.4  
96.8  
1.07  
14.6  
107.0  
1.22  
13.8  
116.00  
1.38  
12.9  
126.0  
1.55  
12.0  
136.0  
1.74  
TCG  
SDT  
KW  
30  
35  
40  
45  
50  
55  
0.809  
0.930  
18.6  
78.3  
0.824  
17.8  
88.0  
0.944  
16.9  
97.8  
1.08  
16.1  
108.0  
1.23  
15.2  
117.  
1.40  
14.3  
127.0  
1.57  
13.4  
137.0  
1.77  
TCG  
SDT  
KW  
20.3  
79.8  
0.841  
19.4  
89.4  
0.962  
18.6  
99.2  
1.10  
17.7  
109.0  
1.25  
16.7  
119.0  
1.42  
15.8  
128.0  
1.60  
14.8  
138.0  
1.79  
TCG  
SDT  
KW  
22.1  
81.6  
0.863  
21.2  
91.0  
0.983  
20.3  
101.0  
1.12  
19.3  
110.0  
1.27  
18.3  
120.0  
1.44  
17.3  
130.0  
1.62  
16.3  
139.0  
1.82  
TCG  
SDT  
KW  
24.0  
83.5  
0.887  
23.1  
92.8  
1.01  
22.1  
102.0  
1.15  
21.1  
112.0  
1.30  
20.0  
122.0  
1.47  
19.0  
131.0  
1.65  
17.8  
141.0  
1.85  
TCG  
SDT  
KW  
26.1  
85.5  
0.914  
25.1  
94.7  
1.03  
24.0  
104.0  
1.17  
22.9  
114.0  
1.33  
21.8  
123.0  
1.50  
20.7  
133.0  
1.68  
19.5  
142.0  
1.89  
TCG  
SDT  
KW  
594D024-E  
TCG  
SDT  
KW  
22.1  
81.1  
1.25  
21.1  
90.3  
1.40  
20.1  
99.6  
1.57  
19.0  
109.0  
1.75  
17.8  
119.0  
1.96  
16.8  
128.0  
2.18  
15.8  
138.0  
2.44  
30  
35  
40  
45  
50  
55  
TCG  
SDT  
KW  
24.2  
83.1  
1.26  
23.2  
92.3  
1.42  
22.1  
102.0  
1.59  
21.0  
111.0  
1.78  
19.8  
120.0  
1.99  
18.6  
130.0  
2.21  
17.5  
139.0  
2.47  
TCG  
SDT  
KW  
26.4  
85.3  
1.28  
25.4  
94.4  
1.44  
24.3  
104.0  
1.62  
23.1  
113.0  
1.81  
21.8  
122.0  
2.02  
20.6  
131.0  
2.25  
19.3  
141.0  
2.51  
TCG  
SDT  
KW  
28.6  
87.6  
1.29  
27.7  
96.6  
1.46  
26.5  
106.0  
1.64  
25.3  
115.0  
1.84  
24.0  
124.0  
2.05  
22.6  
133.0  
2.29  
21.3  
143.0  
2.55  
TCG  
SDT  
KW  
31.0  
90.0  
1.30  
30.1  
99.0  
1.48  
28.9  
108.0  
1.66  
27.6  
117.0  
1.87  
26.3  
126.0  
2.09  
24.8  
135.0  
2.33  
23.4  
145.0  
2.60  
TCG  
SDT  
KW  
33.5  
92.7  
1.32  
32.5  
101.0  
1.49  
31.4  
110.0  
1.69  
30.0  
120.0  
1.90  
28.6  
129.0  
2.13  
27.1  
138.0  
2.38  
25.6  
147.0  
2.65  
594D030-E  
TCG  
SDT  
KW  
28.3  
80.4  
1.47  
27.0  
90.3  
1.72  
25.7  
100.0  
1.99  
24.2  
110.0  
2.30  
22.8  
120.0  
2.63  
21.2  
130.0  
2.99  
19.7  
140.0  
3.34  
30  
35  
40  
45  
50  
55  
TCG  
SDT  
KW  
31.0  
82.0  
1.46  
29.6  
91.9  
1.71  
28.2  
102.0  
1.99  
26.7  
112.0  
2.30  
25.1  
122.0  
2.64  
23.5  
132.0  
3.00  
21.8  
142.0  
3.39  
TCG  
SDT  
KW  
33.9  
83.8  
1.45  
32.4  
93.6  
1.70  
30.9  
104.0  
1.99  
29.3  
113.0  
2.30  
27.6  
123.0  
2.65  
25.9  
133.0  
3.02  
24.1  
144.0  
3.42  
TCG  
SDT  
KW  
36.9  
85.7  
1.44  
35.3  
95.5  
1.70  
33.7  
105.0  
1.98  
32.0  
115.0  
2.30  
30.2  
125.0  
2.66  
28.4  
135.0  
3.04  
26.5  
145.0  
3.45  
TCG  
SDT  
KW  
40.1  
87.8  
1.43  
38.4  
97.4  
1.69  
36.7  
107.0  
1.98  
34.9  
117.0  
2.31  
33.0  
127.0  
2.66  
31.0  
137.0  
3.05  
29.0  
147.0  
3.47  
TCG  
SDT  
KW  
43.5  
90.0  
1.43  
41.7  
99.7  
1.69  
39.8  
109.0  
1.98  
37.9  
119.0  
2.31  
35.9  
129.0  
2.67  
33.8  
139.0  
3.07  
31.7  
149.0  
3.50  
594D036-E  
TCG  
SDT  
KW  
33.8  
77.3  
1.87  
32.3  
87.0  
2.11  
30.7  
96.9  
2.37  
29.1  
107.0  
2.66  
27.4  
117.0  
2.98  
25.7  
126.0  
3.32  
23.9  
136.0  
3.68  
30  
35  
40  
45  
50  
55  
TCG  
SDT  
KW  
37.0  
78.6  
1.89  
35.4  
88.3  
2.12  
33.8  
98.1  
2.39  
32.0  
108.0  
2.68  
30.3  
118.0  
3.00  
28.4  
128.0  
3.35  
26.6  
137.0  
3.72  
TCG  
SDT  
KW  
40.5  
80.3  
1.91  
38.8  
89.8  
2.14  
37.0  
99.5  
2.41  
35.2  
109.0  
2.70  
33.3  
119.0  
3.03  
31.3  
129.0  
3.39  
29.4  
139.0  
3.76  
TCG  
SDT  
KW  
44.1  
82.1  
1.93  
42.3  
91.5  
2.17  
40.5  
101.0  
2.44  
38.5  
111.0  
2.73  
36.5  
121.0  
3.06  
34.4  
130.0  
3.42  
32.3  
140.0  
3.81  
TCG  
SDT  
KW  
48.0  
84.0  
1.96  
46.1  
93.3  
2.20  
44.1  
103.0  
2.47  
42.0  
112.0  
2.76  
39.9  
122.0  
3.10  
37.7  
132.0  
3.46  
35.4  
142.0  
3.86  
TCG  
SDT  
KW  
52.1  
86.1  
1.99  
50.0  
95.3  
2.23  
47.9  
105.0  
2.50  
45.7  
114.0  
2.80  
43.4  
124.0  
3.14  
41.1  
133.0  
3.50  
38.6  
143.0  
3.91  
See notes on page 20.  
—19—  
CONDENSER ONLY RATINGS* Continued  
CONDENSER ENTERING AIR TEMPERATURES °F  
SST  
°F  
55  
65  
75  
85  
95  
105  
115  
594D042-E  
TCG  
SDT  
KW  
39.4  
77.0  
2.17  
37.6  
86.9  
2.43  
35.7  
96.8  
2.72  
33.9  
107.0  
3.04  
32.0  
117.0  
3.40  
30.2  
127.0  
3.81  
28.4  
137.0  
4.26  
30  
35  
40  
45  
50  
55  
TCG  
SDT  
KW  
43.3  
78.5  
2.19  
41.4  
88.2  
2.45  
39.4  
98.0  
2.74  
37.4  
108.0  
3.07  
35.4  
118.0  
3.43  
33.4  
128.0  
3.84  
31.4  
138.0  
4.30  
TCG  
SDT  
KW  
47.5  
80.0  
2.21  
45.4  
89.7  
2.48  
43.3  
99.5  
2.77  
41.1  
109.0  
3.10  
39.0  
119.0  
3.47  
36.8  
129.0  
3.88  
34.6  
139.0  
4.34  
TCG  
SDT  
KW  
51.8  
81.7  
2.24  
49.6  
91.4  
2.51  
47.4  
101.0  
2.80  
45.1  
111.0  
3.14  
42.7  
121.0  
3.51  
40.4  
131.0  
3.92  
38.1  
141.0  
4.39  
TCG  
SDT  
KW  
56.4  
83.6  
2.27  
54.1  
93.2  
2.54  
51.7  
103.0  
2.84  
49.2  
113.0  
3.18  
46.7  
122.0  
3.55  
44.2  
132.0  
3.97  
41.7  
142.0  
4.44  
TCG  
SDT  
KW  
61.2  
85.6  
2.31  
58.8  
95.1  
2.58  
56.2  
105.0  
2.88  
53.6  
114.0  
3.22  
51.0  
124.0  
3.60  
48.3  
134.0  
4.03  
45.6  
144.0  
4.50  
594D048-E, F  
TCG  
SDT  
KW  
46.0  
80.1  
2.46  
43.8  
89.8  
2.82  
41.6  
99.6  
3.22  
39.3  
109.0  
3.65  
36.9  
119.0  
4.13  
34.4  
129.0  
4.64  
32.0  
139.0  
5.17  
30  
35  
40  
45  
50  
55  
TCG  
SDT  
KW  
50.4  
81.9  
2.49  
48.1  
91.6  
2.85  
45.7  
101.0  
3.25  
43.2  
111.0  
3.69  
40.7  
121.0  
4.18  
38.1  
131.0  
4.71  
35.5  
140.0  
5.25  
TCG  
SDT  
KW  
55.1  
83.9  
2.52  
52.6  
93.4  
2.88  
50.1  
103.0  
3.29  
47.4  
113.0  
3.74  
44.7  
123.0  
4.23  
41.9  
132.0  
4.77  
39.1  
142.0  
5.34  
TCG  
SDT  
KW  
60.0  
86.0  
2.55  
57.4  
95.5  
2.92  
54.7  
105.0  
3.33  
51.9  
115.0  
3.79  
49.0  
124.0  
4.29  
46.0  
134.0  
4.84  
43.0  
144.0  
5.43  
TCG  
SDT  
KW  
65.2  
88.3  
2.59  
62.4  
97.7  
2.96  
59.6  
107.0  
3.38  
56.6  
117.0  
3.84  
53.5  
126.0  
4.35  
50.3  
136.0  
4.91  
47.1  
146.0  
5.51  
TCG  
SDT  
KW  
70.7  
90.7  
2.64  
67.7  
100.0  
3.01  
64.6  
109.0  
3.43  
61.5  
119.0  
3.90  
58.2  
128.0  
4.42  
54.8  
138.0  
4.98  
51.3  
148.0  
5.60  
594D060-E  
TCG  
SDT  
KW  
55.1  
80.2  
3.06  
52.7  
89.9  
3.44  
50.1  
99.7  
3.86  
47.4  
109.0  
4.34  
44.8  
119.0  
4.87  
42.2  
129.0  
5.46  
39.5  
139.0  
6.07  
30  
35  
40  
45  
50  
55  
TCG  
SDT  
KW  
60.3  
82.1  
3.10  
57.7  
91.8  
3.49  
55.0  
101.0  
3.92  
52.1  
111.0  
4.40  
49.2  
121.0  
4.93  
46.4  
131.0  
5.53  
43.5  
141.0  
6.17  
TCG  
SDT  
KW  
65.7  
84.1  
3.16  
63.0  
93.7  
3.55  
60.1  
103.0  
3.99  
57.1  
113.0  
4.47  
54.0  
123.0  
5.01  
50.9  
133.0  
5.61  
47.8  
143.0  
6.27  
TCG  
SDT  
KW  
71.4  
86.3  
3.21  
68.6  
95.9  
3.62  
65.6  
105.0  
4.06  
62.3  
115.0  
4.55  
59.0  
125.0  
5.09  
55.6  
135.0  
5.69  
52.3  
144.0  
6.36  
TCG  
SDT  
KW  
77.4  
88.6  
3.28  
74.5  
98.1  
3.69  
71.3  
108.0  
4.14  
67.8  
117.0  
4.64  
64.3  
127.0  
5.19  
60.6  
136.0  
5.79  
57.0  
146.0  
6.46  
TCG  
SDT  
KW  
83.8  
91.1  
3.35  
80.7  
101.0  
3.77  
77.3  
110.0  
4.23  
73.7  
120.0  
4.74  
69.9  
129.0  
5.29  
66.0  
139.0  
5.90  
62.0  
148.0  
6.58  
* ARI listing applies only to systems shown in Performance Data table.  
KW Total Power (Kw)  
SDT — Saturated Temperature Leaving Compressor (°F)  
SST — Saturated Temperature Entering Compressor (°F)  
TCG — Gross Cooling Capacity (1000 Btuh)  
—20—  
SYSTEM DESIGN SUMMARY  
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01 in. wc.  
2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).  
3. Maximum outdoor operating air temperature is 125°F (51.7°C).  
4. For reliable operation, unit should be level in all horizontal planes.  
5. Maximum elevation of indoor coil above or below base of outdoor unit is: Indoor coil above = 50 ft. Indoor coil below = 150 ft.  
6. For interconnecting refrigerant tube lengths greater than 50 ft, consult Residential Split System Long-Line Application Guidelines available from  
equipment distributor.  
7. Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft.  
8. Not more than 3 ft of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical  
rise to the valve connections at the unit. For buried lines longer than 3 ft, consult your local distributor.  
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.  
10. Mix-matches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.  
11. Do not apply capillary tube indoor coils to these units.  
—21—  
MATCHED SYSTEM  
A98599  
—22—  
—23—  
Air-Cooled, Split-System  
Air Conditioner  
GUIDE SPECIFICATIONS  
594D  
1-1/2 to 5 Tons Nominal  
Condenser fan motors will be totally enclosed, 1-phase type  
with class B insulation and permanently lubricated bearings.  
Shafts will be corrosion resistant.  
Fan blades will be statically and dynamically balanced.  
Condenser fan openings will be equipped with steel wire safety  
guards.  
GENERAL  
System Description  
Outdoor-mounted, air-cooled, split-system air conditioner unit  
suitable for ground or rooftop installation. Unit consists of a her-  
metic compressor, an air-cooled coil, propeller-type condenser  
fan, and a control box. Unit will discharge supply air upward as  
shown on contract drawings. Unit will be used in a refrigeration  
circuit to match up to a packaged fan coil or coil unit.  
Compressor  
Compressor will be hermetically sealed.  
Compressor will be mounted on rubber vibration isolators.  
Condenser Coil  
Quality Assurance  
Unit will be rated in accordance with the latest edition of ARI  
Standard 210.  
Unit will be certified for capacity, efficiency, and listed in the latest  
ARI directory.  
Unit construction will comply with latest edition of ANSI/  
ASHRAE and with NEC.  
Unit will be constructed in accordance with UL standards and  
will carry the UL label of approval. Unit will have c-UL approval.  
Unit cabinet will be capable of withstanding Federal Test Method  
Standard No. 141 (Method 6061) 500-hr salt spray test.  
Air-cooled condenser coils will be leak tested at 150 psig and  
pressure tested at 300 psig.  
Condenser coil will be air cooled.  
Coil will be constructed of aluminum fins mechanically bonded  
to copper tubes which are then cleaned, dehydrated, and  
sealed.  
Refrigeration Components  
Refrigeration circuit components will include liquid-line shutoff  
valve with sweat connections, suction line shutoff valves with  
sweat connections, system charge of R22 (R-410A) refrigerant,  
and compressor oil.  
Operating Characteristics  
The capacity of the unit will meet or exceed _____ Btuh at a  
suction temperature of _____ °F.The power consumption at full  
load will not exceed _____ kw.  
Combination of the unit and the evaporator or fan coil unit will  
have a total net cooling capacity of _____ Btuh or greater at  
conditions of _____ CFM entering air temperature at the  
evaporator at _____ °F wet bulb and _____ °F dry bulb, and air  
entering the unit at _____ °F.  
Unit constructed in ISO 9001 approved facility.  
Delivery, Storage, and Handling  
Unit will be shipped as single package only and is stored and  
handled per unit manufacturer’s recommendations.  
Warranty (for inclusion by specifying engineer)  
U.S. and Canada only.  
The system will have an SEER of _____ Btuh/watt or greater at  
DOE conditions.  
PRODUCTS  
Equipment  
Electrical Requirements  
Nominal unit electrical characteristics will be _____ v, single  
phase, 60 hertz. The unit will be capable of satisfactory opera-  
tion within voltage limits of _____ v to _____ v.  
Unit electrical power will be single point connection.  
Control circuit will be 24v.  
Factory assembled, single piece, air-cooled air conditioner unit.  
Contained within the unit enclosure will be all factory wiring,  
piping, controls, compressor, refrigerant charge (R22), and  
special features required prior to field start-up.  
Unit Cabinet  
Unit cabinet will be constructed of galvanized steel, bonderized,  
and coated with a powder coat paint.  
Fans  
Condenser fan will be direct-drive propeller type, discharging air  
upward.  
Special Features  
Refer to section of this literature identifying accessories and  
descriptions for specific features and available enhancements.  
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE  
UNIT MUST BE INSTALLED IN ACCORDANCE  
WITH INSTALLATION INSTRUCTIONS  
Cancels: PDS 594D.18.6  
© 1999 Bryant Heating & Cooling Systems, 7310 W. Morris St. Indpls, IN 46231  
PRINTED IN U.S.A.  
Catalog No. 5259-405 11-99  
—24—  

Briggs Stratton 81996 User Manual
Canon RUNNER C5045 User Manual
Cornelius 569000262 User Manual
Daewoo DWC 072C User Manual
Friedrich MW09C1H User Manual
Frigidaire HOME COMFORT FRA08EZT1 User Manual
Graco Baby Accessories PD216493B User Manual
Graco Baby Accessories PD243008A User Manual
Haier Air Conditioner AC48FS1ERA User Manual
Harbor Freight Tools 96933 User Manual