ELECTRIC
AIR CONDITIONER
Model 594D (60 Hz)
Sizes 018 thru 060
WIDE RANGE OF SIZES—Available in 7 nominal sizes from 018
through 060 to meet the needs for residential and light commercial
applications.
WEATHER-PROTECTIVE CABINET—Steel is galvanized, then
coated with a layer of zinc phosphate to which a coat of modified
polyester powder coating is applied and baked on. This provides
each unit with a hard, smooth finish that will last for many years.
All screws on cabinet exterior are ceramic coated for a long-last-
ing, rust-resistant, quality appearance.
TOTALLY ENCLOSED FAN MOTOR—Means greater reliability
under rain conditions and dependable performance for many
years.The permanent-split capacitor type motor was designed for
optimum efficiency. Then, under extreme conditions, the motor
was tested and qualified to help ensure the greatest reliability.
UNIT DESIGN—Copper tube, enhanced aluminum fin coil is
designed for optimum heat transfer.Vertical air discharge carries
sound and hot condenser air up and away from adjacent patio
areas and foliage. Heat pump style base pan for easy removal of
water, dirt, and leaves.
APPLICATION VERSATILITY—The 594D can be combined
with a wide variety of evaporator coils and blower packages to
provide quiet, dependable comfort. Unit can be installed on a
roof or at ground level on a slab.
EXTERNAL SERVICEVALVES—Both service valves are brass,
back seating type with sweat connections. Valves are externally
located so refrigerant tube connections can be made quickly and
easily. Each valve has a service port for ease of checking oper-
ating refrigerant pressures.
EASY SERVICEABILITY—One panel provides access to elec-
trical controls and compressor. Removal of wire dome grille
gives access to fan motor, while removal of top gives access to
coil.
COMPRESSOR PROTECTION—Each model is protected with
internal temperature- and current-sensitive overloads. An inter-
nal pressure relief valve provides high-pressure protection to the
refrigerant system.
Model 594D Energy-Efficient Air Conditioners incorporate inno-
vative technology to provide quiet, reliable summer cooling per-
formance.Built into these units are the features most desired by
homeowners today, including SEER ratings of up to 12.0 when
used with components as designated by manufacturer.All mod-
els are listed with UL, c-UL, ARI, CEC, and CSA-EEV.
AEROQUIET FAN SYSTEM—Allows air to move through the
unit more easily which lowers sound levels and improves overall
efficiency.
AVAILABLE OPTIONS
SCROLL COMPRESSOR—All units feature the scroll compres-
sor. This compressor is significantly more efficient than conven-
tional compressors. Due to the simplicity of its design, it offers
improved reliability. Each compressor is mounted on rubber iso-
lators for additional sound reduction. Continuous operation is
approved down to 55°F (12.8°C) in the cooling mode. (See cool-
ing performance tables.)
ELECTRICAL RANGE—All units are offered in 208/230-volts,
single phase.
HEAVY DUTY INLET GRILLE—The DuraGuard™ coil pro-
tector, made of a coated steel wire grid with vertical 3/8 in.
spacing, is designed to help protect the coil from inclement
weather, vandalism, and incidental damage. It provides pro-
tection while not restricting airflow and maintaining ease of
coil inspection and cleaning.
LIMITED WARRANTY—Standard 1-year warranty on all parts,
with an additional 9-year warranty on the compressor.
Form No. PDS 594D.18.7
RECOMMENDED TUBE DIAMETERS
LIQUID TUBE DIAMETER (IN.)
VAPOR TUBE DIAMETER (IN.)
UNIT
SIZE
0 to 50 Ft
Tube Length
0 to 50 Ft
Tube Length
Long-Line Applications*
(Maximum Diameter)
Long-Line Applications*
018, 024
030, 036
042, 048
060
5/8
3/4
3/4
7/8
3/8
3/8
7/8
1-1/8
1-1/8
1-1/8
* For tube sets between 50 and 175 ft, consult Residential Split System Long-Line Application Guideline.
CHECK-FLO-RATER®
PISTON*
UNIT SIZE-SERIES
IDENTIFICATION NO.
018, E
55
59
67
73
78
84
93
024, E
030, E
036, E
042, E
048, E,F
060, E
* Piston listed is for any approved non-capillary tube coil combination.
Piston is shipped with outdoor unit and must be installed in an approved
indoor coil.
SOUND POWER (dBA)
OCTAVE BAND CENTER FREQUENCY (Hz)
UNIT
SIZE
SOUND
LEVEL (dBA)
125
54.5
51.5
57.0
59.0
58.0
60.0
61.5
250
63.0
61.0
64.0
66.0
65.0
64.0
64.5
500
65.5
62.5
67.0
67.0
67.5
68.5
69.0
1000
66.0
65.5
69.0
69.5
69.0
68.5
70.0
2000
63.5
62.0
64.0
66.5
65.5
67.5
68.0
4000
59.0
58.5
60.0
62.5
61.0
64.5
66.0
8000
51.5
52.5
52.5
56.0
54.0
59.5
60.5
018
024
030
036
042
048
060
72
74
74
76
76
78
78
P
REGISTERED QUALITY SYSTEM
CERTIFICATION APPLIES ONLY
WHEN THE COMPLETE SYSTEM
IS LISTED WITH ARI
—3—
SPECIFICATIONS
UNIT SIZE - SERIES
OPERATING WT (Lb)
018-E
138
024-E
143
030-E
146
036-E
200
ELECTRICAL
Unit Volts—Hertz—Phase
Operating Voltage Range*
Compressor— Rated Load Amps
Locked Rotor Amps
208/230—60—1
208/230—60—1
208/230—60—1
208/230—60—1
187—253
8.9
187—253
11.4
56.0
0.5
187—253
13.7
72.5
0.8
187—253
16.0
88.0
1.1
41.0
0.5
Condenser Fan Motor—Full Load Amps
Min Unit Ampacity for Wire Sizing
Min Wire Size (60°C Copper) AWG†
Min Wire Size (75°C Copper) AWG†
Max Wire Length (60°C) (Ft)‡
Max Wire Length (75°C) (Ft)‡
Max Branch Circuit Fuse Size**
COMPRESSOR AND REFRIGERANT
Compressor—Manufacturer & Type
Temperature & Current Protection
Refrigerant—R-22 Amount (Lb)
CONDENSER COIL AND FAN
Coil Face Area (Sq Ft)
11.6
14
14.8
14
17.9
14
21.1
12
14
14
14
12
61
53
56
66
58
50
53
63
20
20
25
30
Copeland Scroll
Internal Line Break
4.00
7.27
4.25
4.50
5.53
12.0
8.8
Fins per In.—Rows—Circuits
Fan Motor—HP, Type, & RPM
Volts—Hertz—Phase
20—1—1
25—1—2
1/12 PSC & 1100
1/10 PSC & 1100
208/230—60—1
1/5 PSC & 825
3000
Condenser Airflow (CFM)
OPTIONAL EQUIPMENT
Support Feet Kit
1700
2000
KSASF0101AAA
KAACF0601SML
KAATD0101TDR
Coastal Filter
KAACF0201MED
Time-Delay Relay
Cycle Protector
KSACY0101AAA
KAACH1201AAA
KSAHS1501AAA
KAACS0201PTC
Crankcase Heater
Start Assist—Capacitor/Relay Type
Start Assist—PTC Type
TXV Kit (RPB)
KAATX0201RPB
KAATX0301RPB
KAATX0401RPB
KAATX0501RPB
TXV Kits (Hard Shutoff)
Low-Pressure Switch
KSATX0601HSO
KAALP0101LPS
KSAHI0101HPS
P502-8083S (RCD)
KAAFT0101AAA
KAALS0101LLS
KAAWS0101AAA
KSALA0201R22
P251-0083 (RCD)
32LT660004 (RCD)
High-Pressure Switch
Filter Drier
Evaporator Freeze Thermostat††
Liquid-Line Solenoid Valve
Winter Start Control††
Low-Ambient Kit
Low-Ambient Controller
MotorMaster® Control‡‡
Ball Bearing Fan Motor
HC34GE232 (RCD)
HC38GE231 (RCD)
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
TSTATBBPAC01-B
TSTATBBBAC01-B
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
Builder’s Thermostat, Manual
Changeover, Non-Programmable,
°F/°C, 1-Stage Heat, 1-Stage Cool
Thermidistat™ Control—Programmable/
Non-Programmable Thermostat with
Humidity Control
TSTATBBPRH01-B
TSTATXXSEN01-B
Outdoor Air Temperature Sensor
Backplate for Non-Programmable
Thermostat
TSTATXXNBP01
TSTATXXBBP01
TSTATXXPBP01
Backplate for Builder’s Thermostat
Backplate for Programmable Thermostat
Thermostat Conversion Kit (4 to 5 wire)
— 10 Pack
TSTATXXCNV10
See notes on page 5.
—4—
SPECIFICATIONS Continued
UNIT SIZE - SERIES
OPERATING WT (Lb)
042-E
213
048-E/F
060-E
287
247
ELECTRICAL
Unit Volts—Hertz—Phase
Operating Voltage Range*
Compressor— Rated Load Amps
Locked Rotor Amps
208/230—60—1
208/230—60—1
187—253
23.7/21.3
129.0/137.0
1.4
208/230—60—1
187—253
20.0
104.0
1.1
187—253
28.8
169.0
1.4
Condenser Fan Motor—Full Load Amps
Min Unit Ampacity for Wire Sizing
Min Wire Size (60°C Copper) AWG†
Min Wire Size (75°C Copper) AWG†
Max Wire Length (60°C) (Ft)‡
Max Wire Length (75°C) (Ft)‡
Max Branch Circuit Fuse Size**
COMPRESSOR AND REFRIGERANT
Compressor—Manufacturer & Type
Temperature & Current Protection
Refrigerant—R-22 Amount (Lb)
CONDENSER COIL AND FAN
Coil Face Area (Sq Ft)
26.1
10
31.0/28.0
8/10
37.4
8
10
10
8
96
71
104
99
91
68
40
50/40
60
Copeland Scroll
Internal Line Break
6.34
6.68
9.25
15.2
18.3
Fins per In.—Rows—Circuits
Fan Motor—HP, Type, & RPM
Volts—Hertz—Phase
25—1—3
25—1—4
1/5 PSC & 825
3000
1/4 PSC & 1100
3300
208/230—60—1
Condenser Airflow (CFM)
OPTIONAL EQUIPMENT
Support Feet Kit
KSASF0101AAA
KAACF0201MED
KAATD0101TDR
Coastal Filter
Time-Delay Relay
Cycle Protector
KSACY0101AAA
Standard
Crankcase Heater
KAACH1201AAA
Start Assist—Capacitor/Relay Type
Start Assist—PTC Type
TXV Kit (RPB)
KSAHS1501AAA
KSAHS1601AAA
KAATX0701RPB
KAACS0201PTC
KAATX0601RPB
KAATX0501RPB
KSATX0601HSO
TXV Kits (Hard Shutoff)
Low-Pressure Switch
KSATX0701HSO
KAALP0101LPS
KSAHI0101HPS
P502-8163S (RCD)
KAAFT0101AAA
KAALS0101LLS
KAAWS0101AAA
KSALA0201R22
P251-0083 (RCD)
32LT660004 (RCD)
High-Pressure Switch
Filter Drier
Evaporator Freeze Thermostat††
Liquid-Line Solenoid Valve
Winter Start Control††
Low-Ambient Kit
Low-Ambient Controller
MotorMaster® Control‡‡
Ball Bearing Fan Motor
HC38GE231 (RCD)
HC40GE232 (RCD)
Thermostat, Auto Changeover,
Non-Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
TSTATBBNAC01-B
TSTATBBPAC01-B
TSTATBBBAC01-B
Thermostat, Auto Changeover,
7-Day Programmable, °F/°C,
1-Stage Heat, 1-Stage Cool
Builder’s Thermostat, Manual
Changeover, Non-Programmable,
°F/°C, 1-Stage Heat, 1-Stage Cool
Thermidistat™ Control—Programmable/
Non-Programmable Thermostat with
Humidity Control
TSTATBBPRH01-B
TSTATXXSEN01-B
Outdoor Air Temperature Sensor
Backplate for Non-Programmable
Thermostat
TSTATXXNBP01
TSTATXXBBP01
TSTATXXPBP01
Backplate for Builder’s Thermostat
Backplate for Programmable Thermostat
Thermostat Conversion Kit (4 to 5 wire)
— 10 Pack
TSTATXXCNV10
*
Permissible limits of the voltage range at which the unit will operate satisfactorily. Operation outside these limits may result in unit failure.
Copper wire must be used from service disconnect to unit.
†
If wire is applied at ambient greater than 30°C (86°F), consult Table 310-16 of the NEC (ANSI/NFPA 70).
The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60°C (140°F) conductors, per the NEC (ANSI/NFPA 70)
Article 336-26.
‡
Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2 percent.
All motors/compressors contain internal overload protection.
** Time-delay fuse.
†† Use with Low-Ambient Controller.
‡‡ Fan motor with ball bearings required.
—5—
ACCESSORY USAGE GUIDELINE
REQUIRED FOR
LOW-AMBIENT
APPLICATIONS
(Below 55°F)
REQUIRED FOR
REQUIRED FOR
SEA COAST
APPLICATIONS
(Within 2 Miles)
LONG-LINE
APPLICATIONS*
(Over 50 Ft)
ACCESSORY
Crankcase Heater
Yes
Yes
Yes†
No
Yes
No
No
No
No
No
No
No
Evaporator Freeze Thermostat
Winter Start Control
Accumulator
Compressor Start Assist
Capacitor and Relay
Yes
Yes
Yes
No
No
No
Low-Ambient Controller
or
MotorMaster® Control
Wind Baffle
Coastal Filter
Support Feet
See Low-Ambient Instructions
No
No
No
No
Yes
No
Recommended
Recommended
Liquid-Line Solenoid Valve
See Long-Line
Application
Guideline
or
No
No
No
Hard Shutoff TXV
Ball Bearing Fan Motor
Yes
No
* For tubing line sets between 50 and 175 ft, refer to Residential Split System Long-Line Application Guideline.
† Only when low-pressure switch is used.
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)
1. Ball Bearing Fan Motor
A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication.
SUGGESTED USE: Required on all units where Low-Ambient Controller (full modulation feature) or MotorMaster® Control has been added.
2. Coastal Filter
A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from corrosive atmosphere without restricting airflow.
SUGGESTED USE: In geographic areas where salt damage could occur.
In areas with high pollution levels.
3. Compressor Start Assist—Capacitor/Relay Type
Start capacitor and start relay gives “hard” boost to compressor motor at each start-up.
SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.
Installations where outdoor design temperature exceeds 105°F (40.6°C).
Replacement installations with hard shutoff expansion valve on indoor coil.
Installations where Liquid-Line Solenoid Valve has been added.
4. Compressor Start Assist—PTC Type
Solid state electrical device which gives a ‘‘soft’’ boost to compressor motor at each start-up.
SUGGESTED USE: Installations with marginal power supply.
Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.
5. Crankcase Heater
An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication
on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.
SUGGESTED USE: When interconnecting tube length exceeds 50 ft.
When unit will be operated below 55°F (12.8°C) outdoor air temperature. Use with Low-Ambient Controller.
All commercial installations.
6. Cycle Protector
Solid state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has
been interrupted for any reason, including normal room thermostat cycling.
SUGGESTED USE: Installations in areas where power interruptions are frequent.
Where user is likely to “play” with the room thermostat.
All commercial installations.
Installations where interconnecting tube length exceeds 50 ft.
High-rise applications.
7. Evaporator Freeze Thermostat
An SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions.
SUGGESTED USE: All units where Winter Start Control has been added. Use with Low-Ambient Controller.
8. Filter Drier
A device for removing contaminants from refrigerant circulating in an air conditioner: 1 direction flow.
SUGGESTED USE: All split-system air conditioners.
9. High-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to 400 ± 10
psig and resets at 298 ± 20 psig. Provides protection against compressor damage due to loss of outdoor airflow. To prevent rapid compressor recycling,
Cycle Protector can be used with this switch.
SUGGESTED USE: Installations exposed to very ‘‘dirty’’ outdoor air.
Installations where condenser inlet air temperature exceeds 125°F (51.7°C).
10. Liquid-Line Solenoid Valve (LSV)
An electrically operated shutoff valve to be installed at the outdoor or indoor unit (depending on tubing configuration) which stops and starts refrigerant
liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle.
Note: Compressor Start Assist—Capacitor/Relay Type must also be used. Do not use with hard shutoff TXV.
SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
In certain long-line applications. Refer to Residential Split System Long-Line Application Guideline.
—6—
ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically) Continued
11. Low-Ambient Controller
Head pressure controller is a cycle control device activated by a temperature sensor mounted on a header tube of the outdoor coil. It is designed to cycle
the outdoor fan motor in order to maintain condensing temperature within normal operating limits (approximately 100°F high and 60°F low).The control will
maintain working head pressure at low-ambient temperatures down to 0°F when properly installed.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F (12.8°C).
12. Low-Pressure Switch
Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27
psig. Prevents indoor coil freeze-up due to loss of indoor airflow. Provides protection against compressor damage due to loss of refrigerant charge. To
prevent rapid compressor recycling, Cycle Protector can be used with this switch.
SUGGESTED USE: Where indoor coil is exposed to ‘‘dirty’’ air.
All commercial installations.
13. MotorMaster® Control
A fan speed control device activated by a temperature sensor. Designed to control condenser fan motor speed in response to the saturated, condensing
temperature during operation in cooling mode only. For outdoor temperatures down to –20°F, it maintains condensing temperature at 100°F ± 10°F.
SUGGESTED USE: Cooling operation at outdoor temperatures below 55°F.
All commercial installations.
14. Outdoor Air Temperature Sensor
A device that allows the temperature at a remote location (outdoors) to be displayed at the thermostat.
SUGGESTED USE: All corporate programmable thermostats.
15. Support Feet
Four stick-on plastic feet which raise the unit 4 in. above the mounting pad. This allows sand, dirt, and other debris to be flushed from the unit base,
minimizing corrosion.
SUGGESTED USE: Coastal installations.
Windy areas or where debris is normally circulating.
Rooftop installations.
16. Thermostatic Expansion Valve (TXV)
A modulating flow control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the
evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shutoff and RPB type valves are available.
SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
Required for use on all zoning systems.
17. Time-Delay Relay
An SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.
SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. Refer to ARI Unitary Directory.
Required for use on all zoning systems.
18. Winter Start Control
An SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load conditions.
SUGGESTED USE: All air conditioners where Low-Ambient Controller has been added.
—7—
COMBINATION RATINGS
SEER
FACTORY
SUPPLIED
ENHANCE-
MENT
BRYANT GAS
FURNACE OR
STANDARD ACCESSORY ACCESSORY
UNIT
SIZE-SERIES
INDOOR
MODEL
TOT. CAP.
BTUH
RATING
TDR†
TXV‡
EERA
CK5A/CK5BA024*
CC5A/CD5AA018
CC5A/CD5AA024
CC5A/CD5AW024
CE3AA024
17,600
17,200
17,600
17,600
17,600
17,600
17,200
17,600
16,800
17,600
17,600
17,000
17,600
17,000
18,000
18,000
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
TDR
10.50
10.50
10.50
10.50
10.50
10.50
10.50
10.50
11.00
11.00
11.00
10.50
10.50
10.50
12.50
12.50
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
—
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
—
10.60
10.45
10.60
10.60
10.60
10.60
10.45
10.60
10.40
10.75
10.60
10.70
10.65
10.45
12.05
12.10
CK3BA024
CK5A/CK5BA018
CK5A/CK5BW024
F(A,B)4AN(F,C)018
F(A,B)4AN(F,C)024
FC4BNF024
FF1(B,C,D)NA018
FF1(B,C,D)NA024
FG3AAA024
FK4CNF001
FK4CNF002
TDR
—
TDR&TXV
TDR
TDR
NONE
TDR&TXV
TDR&TXV
—
—
11.00
11.00
11.00
—
—
11.00
—
018-E
—
—
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
CC5A/CD5AA018
CC5A/CD5AA024
CK5A/CK5BA018
CK5A/CK5BA024
17,000
17,600
17,000
17,600
TDR
TDR
TDR
TDR
12.50
13.00
12.50
13.00
—
—
—
—
12.50
13.00
12.50
13.00
11.40
11.80
11.40
11.80
COILS + 355MAV042060 VARIABLE SPEED FURNACE
CC5A/CD5AW024
CK5A/CK5BW024
17,600
17,600
TDR
TDR
13.00
13.00
—
—
13.00
13.00
11.60
11.60
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CC5A/CD5AW024
CK5A/CK5AW024
17,600
17,600
TDR
TDR
13.00
13.00
—
—
13.00
13.00
11.70
11.70
CC5A/CD5AA030*
CC5A/CD5AA024
CC5A/CD5AW024
CC5A/CD5AW030
CE3AA024
23,000
23,000
23,000
23,200
23,000
23,200
23,000
23,000
23,000
23,000
23,000
23,000
23,200
23,000
23,400
23,000
23,400
23,000
23,400
22,600
24,000
24,200
24,400
NONE
NONE
10.80
10.80
10.80
10.80
10.80
11.00
10.80
10.80
10.80
10.80
10.80
10.80
10.80
11.00
11.40
11.00
11.40
11.00
11.30
10.50
12.50
12.70
13.00
11.00
11.00
11.00
11.00
11.00
11.30
11.00
11.00
11.00
11.00
11.00
11.00
11.00
—
11.00
11.00
11.00
11.00
11.00
11.30
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.40
—
9.80
9.70
9.70
9.80
9.80
9.80
9.80
9.70
9.80
9.70
9.80
9.70
9.80
9.80
10.00
9.80
10.00
9.70
9.90
9.60
10.95
11.05
11.30
NONE
NONE
NONE
CE3AA030
NONE
CF5AA024
NONE
CK3BA024
NONE
CK3BA030
NONE
CK5A/CK5BA024
CK5A/CK5BA030
CK5A/CK5BW024
CK5A/CK5BW030
F(A,B)4AN(F,C)024
F(A,B)4AN(F,C)030
FC4BNF024
NONE
NONE
NONE
NONE
TDR
TDR
—
TDR & TXV
TDR & TXV
TDR
—
FC4BNF030
—
—
FF1(B,C,D))NA024
FF1(B,C,D))NA030
FG3AAA024
—
11.00
11.30
11.00
—
—
—
TDR
NONE
TDR & TXV
TDR & TXV
TDR & TXV
—
024-E
11.00
—
FK4CNF001
FK4CNF002
—
—
FK4CNF003
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
CC5A/CD5AA030
CE3AA030
CK5A/CK5BA030
23,200
23,200
23,200
TDR
TDR
TDR
12.00
12.00
12.00
—
—
—
12.00
12.00
12.00
10.75
10.85
10.75
COILS + 355MAV042040 VARIABLE SPEED FURNACE
CC5A/CD5AA030
CK5A/CBA5030
23,200
23,200
TDR
TDR
12.00
12.00
—
—
12.00
12.00
10.70
10.70
COILS + 355MAV042060 VARIABLE SPEED FURNACE
CC5A/CD5AA030
CK5A/CK5BA030
23,200
23,200
TDR
TDR
12.00
12.00
—
—
12.00
12.00
10.70
10.70
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CC5A/CD5AA030
CK5A/CK5BA030
23,200
23,200
TDR
TDR
12.00
12.00
—
—
12.00
12.00
10.70
10.70
CC5A/CD5AA036*
CC5A/CD5AA030
CC5A/CD5AW030
CD5AW036
29,000
28,200
28,200
29,000
28,400
28,800
29,000
28,200
29,000
28,200
29,000
28,200
29,000
28,200
28,600
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
TDR
10.80
10.40
10.40
10.80
10.50
10.60
10.60
10.40
10.80
10.40
10.80
10.50
10.80
11.00
10.80
11.00
10.60
10.60
11.00
10.80
11.00
11.00
10.60
11.00
10.60
11.00
10.60
11.00
—
11.00
10.60
10.60
11.00
10.80
11.00
11.00
10.60
11.00
10.60
11.00
10.60
11.00
11.00
10.80
9.60
9.30
9.30
9.60
9.40
9.50
9.55
9.30
9.60
9.30
9.60
9.30
9.60
9.45
9.35
CE3AA030
CE3AA036
CF5AA036
030-E
CK3BA030
CK3BA036
CK5A/CK5BA030
CK5A/CK5BA036
CK5A/CK5BW030
CK5A/CK5BW036
F(A,B)4AN(F,C)030
F(A,B)4AN(F,C)036
TDR
—
See notes on page 11.
—8—
COMBINATION RATINGS Continued
SEER
FACTORY
SUPPLIED
ENHANCE-
MENT
BRYANT GAS
FURNACE OR
STANDARD ACCESSORY ACCESSORY
UNIT
SIZE-SERIES
INDOOR
MODEL
TOT. CAP.
BTUH
RATING
TDR†
TXV‡
EERA
FC4BNF030
FC4BNF036
28,200
28,600
28,400
28,600
29,200
29,400
29,600
TDR & TXV
TDR & TXV
TDR
11.00
10.80
11.00
10.50
11.50
11.80
12.00
—
—
—
—
9.45
9.35
FF1(B,C,D)NA030
FG3AAA036
FK4CNF001
—
11.00
10.80
—
9.40
NONE
10.80
—
—
—
9.40
TDR & TXV
TDR & TXV
TDR & TXV
10.05
10.10
10.55
FK4CNF002
FK4CNF003
—
—
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
CC5A/CD5AA036
CE3AA036
CK5A/CK5BA036
29,400
29,000
29,400
TDR
TDR
TDR
12.20
12.00
12.00
—
—
—
12.20
12.00
12.00
10.45
10.30
10.45
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE
030-E
CC5A/CD5AA036
CE3AA036
CK5A/CK5BA036
29,400
29,000
29,400
TDR
TDR
TDR
12.20
12.00
12.00
—
—
—
12.20
12.00
12.00
10.45
10.30
10.45
COILS + 355MAV042040 VARIABLE SPEED FURNACE
CC5A/CD5AA036
CK5A/CK5BA036
29,400
29,400
TDR
TDR
12.00
11.80
—
—
12.00
11.80
10.40
10.40
COILS + 355MAV042060 VARIABLE SPEED FURNACE
CC5A/CD5A036
CK5A/CK5BA036
29,400
29,400
TDR
TDR
12.00
11.80
—
—
12.00
11.80
10.40
10.40
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CC5A/CD5AA036
CK5A/CK5BA036
29,400
29,400
TDR
TDR
12.00
12.00
—
—
12.00
12.00
10.40
10.40
CC5A/CD5AA042*
CC5A/CD5AA036
CC5A/CD5AW042
CD5AW036
35,000
35,000
34,800
35,000
34,400
35,000
35,000
35,000
35,000
35,000
35,000
35,000
34,800
35,000
34,400
36,600
34,400
35,000
36,000
34,200
36,200
34,600
34,800
35,000
36,000
NONE
NONE
11.00
11.00
11.00
11.00
10.80
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.20
11.00
12.00
11.00
11.20
11.50
10.80
13.00
11.50
11.50
12.00
12.50
11.20
11.20
11.20
11.20
11.00
11.20
11.20
11.20
11.20
11.20
11.20
11.20
11.20
—
11.20
11.20
11.20
11.20
11.00
11.20
11.20
11.20
11.20
11.20
11.20
11.20
11.20
11.20
11.00
—
10.15
10.15
10.05
10.15
10.05
10.20
10.10
10.15
10.15
10.15
10.15
10.15
10.05
10.10
9.80
NONE
NONE
CE3AA036
NONE
CE3AA042
NONE
CF5AA036
NONE
CK3BA036
NONE
CK3BA042
NONE
CK5A/CK5BA036
CK5A/CK5BA042
CK5A/CK5BW036
CK5A/CK5BW042
F(A,B)4AN(F,B,C))042
F(A,B)4AN(F,C)036
FC4BNB054
NONE
NONE
NONE
NONE
TDR
TDR
—
TDR & TXV
TDR & TXV
TDR & TXV
TDR & TXV
NONE
—
10.80
9.80
FC4BNF036
—
—
FC4BN(F,B)042
FC4BNF038
—
—
—
10.10
9.80
9.95
10.65
10.35
10.35
10.95
11.40
—
FG3AAA036
11.00
—
11.00
—
FK4CNB006
TDR & TXV
TDR & TXV
TDR & TXV
TDR & TXV
TDR & TXV
FK4CNF001
—
—
FK4CNF002
—
—
FK4CNF003
—
—
FK4CNF005
—
—
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
CC5A/CD5AA042
CE3AA042
CK5A/CK5BA036
34,600
34,600
35,000
TDR
TDR
TDR
12.00
12.00
12.00
—
—
—
12.00
12.00
12.00
10.75
10.75
10.75
036-E
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE
CC5A/CD5AA042
CE3AA042
CK5A/CK5BA042
34,600
34,600
35,000
TDR
TDR
TDR
12.00
12.00
12.00
—
—
—
12.00
12.00
12.00
10.75
10.75
10.75
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
CC5A/CD5AA042
CE3AA042
CK5A/CK5BA042
34,600
34,600
35,000
TDR
TDR
TDR
12.00
12.00
12.00
—
—
—
12.00
12.00
12.00
10.75
10.75
10.75
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE
CC5A/CD5AA042
CE3AA042
CK5A/CK5BA042
34,600
34,600
35,000
TDR
TDR
TDR
12.00
12.00
12.00
—
—
—
12.00
12.00
12.00
10.75
10.75
10.75
COILS + 355MAV042040 VARIABLE SPEED FURNACE
CC5A/CD5AA042
CK5A/CK5BA042
34,600
35,000
TDR
TDR
12.00
12.00
—
—
12.00
12.00
10.75
10.75
COILS + 355MAV042060 VARIABLE SPEED FURNACE
CC5A/CD5AA042
CK5A/CK5BA042
34,600
34,600
TDR
TDR
12.00
12.00
—
—
12.00
12.00
10.75
10.75
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CC5A/CD5AA042
CK5A/CK5BA042
34,600
35,000
TDR
TDR
12.00
12.00
—
—
12.00
12.00
10.75
10.75
COILS + 355MAV060100 VARIABLE SPEED FURNACE
CC5A/CD5AA042
CK5A/CK5BA042
34,600
34,600
TDR
TDR
12.00
12.00
—
—
12.00
12.00
10.75
10.75
See notes on page 11.
—9—
COMBINATION RATINGS Continued
SEER
FACTORY
SUPPLIED
ENHANCE-
MENT
BRYANT GAS
FURNACE OR
STANDARD ACCESSORY ACCESSORY
UNIT
SIZE-SERIES
INDOOR
MODEL
TOT. CAP.
BTUH
RATING
TDR†
TXV‡
EERA
CD5AA048*
CC5A/CD5AA042
CC5A/CD5AC048
CC5A/CD5AW042
CC5A/CD5AW048
CE3AA042
41,000
41,000
40,500
40,500
41,000
41,000
41,500
41,500
41,000
41,000
41,000
41,000
40,500
41,000
41,000
41,500
42,500
41,000
41,500
41,000
42,500
41,000
42,000
NONE
NONE
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.20
11.50
12.50
11.20
11.50
11.00
13.00
12.00
12.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
—
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.50
11.20
11.50
—
10.25
10.25
10.15
10.15
10.25
10.30
10.35
10.30
10.25
10.25
10.25
10.25
10.15
10.25
10.10
10.30
10.95
10.10
10.30
10.25
11.65
10.85
11.30
NONE
NONE
NONE
NONE
CE3AA048
NONE
CF5AA048
NONE
CK3BA042
NONE
CK3BA048
NONE
CK5A/CK5BA042
CK5A/CK5BA048
CK5A/CK5BW042
CK5A/CK5BW048
F(A,B)4AN(F,B,C)042
F(A,B)4AN(F,B,C)048
FC4BNB054
NONE
NONE
NONE
NONE
TDR
TDR
—
TDR & TXV
TDR & TXV
TDR & TXV
NONE
—
FC4BN(F,B)042
FC4BN(F,B)048
FG3AAA048
—
—
—
—
11.50
—
11.50
—
FK4CNB006
TDR & TXV
TDR & TXV
TDR & TXV
FK4CNF003
—
—
—
—
042-E
FK4CNF005
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE
CD5AA048
CE3AA048
CK5A/CK5BA048
41,000
41,000
41,000
TDR
TDR
TDR
12.50
12.50
12.50
—
—
—
12.50
12.50
12.50
11.10
11.05
11.10
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
CD5AA048
CE3AA048
CK5A/CK5BA048
41,000
41,000
41,000
TDR
TDR
TDR
12.50
12.50
12.50
—
—
—
12.50
12.50
12.50
11.10
11.05
11.10
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE
CD5AA048
CE3AA048
CK5A/CK5BA048
41,000
41,000
41,000
TDR
TDR
TDR
12.50
12.50
12.50
—
—
—
12.50
12.50
12.50
11.10
11.05
11.10
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CD5AA048
CK5A/CK5BA048
41,000
41,000
TDR
TDR
12.50
12.00
—
—
12.50
12.00
11.15
11.15
COILS + 355MAV060100 VARIABLE SPEED FURNACE
CD5AA048
CK5A/CK5BA048
41,000
41,000
TDR
TDR
12.50
12.50
—
—
12.50
12.50
11.15
11.15
*CC5A/CD5AA060
CC5A/CD5AC048
CC5A/CD5AW048
CC5A/CD5AW060
CD5AA048
46,800
45,000
46,000
48,000
46,500
46,500
48,000
46,500
46,500
46,800
46,500
46,800
45,000
47,000
46,500
46,800
46,500
48,000
46,500
48,000
48,000
47,000
48,000
48,000
48,000
46,000
47,500
48,500
48,000
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
NONE
TDR
10.60
10.50
10.50
10.80
10.50
10.70
11.00
10.70
10.50
10.60
10.50
10.60
10.50
10.50
10.50
10.60
10.50
10.80
11.00
11.00
11.50
11.00
11.00
11.50
11.00
10.50
10.70
12.50
12.20
11.00
10.80
11.00
11.20
11.00
11.00
11.20
11.10
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.20
—
11.00
10.80
11.00
11.20
11.00
11.00
11.20
11.10
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.00
11.20
11.00
11.00
11.50
—
9.65
9.50
9.60
9.85
9.60
9.70
9.95
9.70
9.65
9.85
9.65
9.85
9.65
10.05
9.65
9.85
9.65
10.05
9.60
9.70
10.00
9.60
9.70
10.05
10.00
9.60
9.80
10.85
10.55
CE3AA048
CE3AA060
CF5AA048
CK3BA048
CK3BA060
CK5A/CK5BA048
CK5A/CK5BA060
CK5A/CK5BN048
CK5A/CK5BN060
CK5A/CK5BT048
CK5A/CK5BT060
CK5A/CK5BW048
CK5A/CK5BX060
F(A,B)4AN(F,B,C)048
F(A,B)4AN(F,B,C)060
FB4ANB070
TDR
—
TDR
—
048-E/F
FC4BN(F,B)048
FC4BN(F,B)060
FC4BNB054
TDR & TXV
TDR & TXV
TDR & TXV
TDR & TXV
NONE
NONE
TDR
—
—
—
—
—
—
FC4BNB070
—
FG3AAA048
10.80
11.00
—
10.80
11.00
—
FG3AAA060
FK4CNB006
FK4CNF005
TDR
—
—
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE
CC5A/CD5AC048
CD5AA048
45,000
46,000
46,000
46,000
TDR
TDR
TDR
TDR
11.00
11.00
11.00
11.00
—
—
—
—
11.00
11.00
11.00
11.00
9.65
9.75
9.80
9.80
CK3BA048
CK5A/CK5BA048
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AW048
CC5A/CD5AW060
CK3BA060
CK5A/CK5BA060
CK5A/CK5BW048
CK5A/CK5BX060
47,000
46,000
47,000
47,000
47,000
46,000
47,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11.50
11.20
12.00
11.50
11.50
11.20
12.00
—
—
—
—
—
—
—
11.50
11.20
12.00
11.50
11.50
11.20
12.00
10.25
10.10
10.55
10.45
10.45
10.20
10.70
See notes on page 11.
—10—
COMBINATION RATINGS Continued
SEER
FACTORY
SUPPLIED
ENHANCE-
MENT
BRYANT GAS
FURNACE OR
STANDARD ACCESSORY ACCESSORY
UNIT
SIZE-SERIES
INDOOR
MODEL
TOT. CAP.
BTUH
RATING
TDR†
TXV‡
EERA
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AW048
CC5A/CD5AW060
CK3BA060
CK5A/CK5BA060
CK5A/CK5BW048
CK5A/CK5BX060
46,500
46,000
47,000
46,500
46,500
46,000
47,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11.50
11.20
12.00
11.50
11.50
11.20
12.00
—
—
—
—
—
—
—
11.50
11.20
12.00
11.50
11.50
11.20
12.00
10.15
10.05
10.45
10.35
10.35
10.10
10.60
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CD5AA048
CK3BA048
CK5A/CK5BA048
46,000
46,000
46,000
TDR
TDR
TDR
11.00
11.00
11.00
—
—
—
11.00
11.00
11.00
9.70
9.75
9.75
COILS + 355MAV060080 VARIABLE SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AW060
CD5AA048
46,000
47,000
46,000
46,000
46,500
47,000
46,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11.00
11.20
11.00
11.00
11.00
11.20
11.00
—
—
—
—
—
—
—
11.00
11.20
11.00
11.00
11.00
11.20
11.00
9.70
9.95
9.60
9.70
9.90
10.15
9.70
CK3BA048
CK5A/CK5BA060
CK5A/CK5BX060
CK5A/CK5BA048
048-E/F
COILS + 355MAV060100 VARIABLE SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AC048
CC5A/CD5AW060
CD5AA048
46,000
45,000
47,000
46,000
46,000
46,500
46,000
46,000
47,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11.20
11.00
11.80
11.00
11.00
11.20
11.00
11.20
11.80
—
—
—
—
—
—
—
—
—
11.20
11.00
11.80
11.00
11.00
11.20
11.00
11.20
11.80
9.95
9.70
10.20
9.90
CK3BA048
9.95
CK3BA060
10.15
9.95
CK5A/CK5BA048
CK5A/CK5BA060
CK5A/CK5BX060
10.40
10.40
COILS + 355MAV060120 VARIABLE SPEED FURNACE
CC5A/CD5AA060
CC5A/CD5AW048
CC5A/CD5AW060
CK3BA060
CK5A/CK5BA060
CK5A/CK5BW048
CK5A/CK5BX060
46,000
46,000
47,000
46,500
46,000
46,000
47,000
TDR
TDR
TDR
TDR
TDR
TDR
TDR
11.20
11.20
11.80
11.20
11.20
11.20
11.80
—
—
—
—
—
—
—
11.20
11.20
11.80
11.20
11.20
11.20
11.80
9.95
9.90
10.25
10.20
10.20
9.95
10.45
CC5A/CD5AW060*
CC5A/CD5AA060
CE3AA060
56,500
54,500
56,500
54,500
56,500
57,000
57,500
57,500
57,000
56,000
57,500
NONE
NONE
10.80
10.60
10.80
10.60
10.80
10.80
11.00
11.00
10.80
10.80
12.00
11.00
10.80
11.00
10.80
11.00
—
11.00
10.80
11.00
10.80
11.00
10.80
11.00
—
9.70
9.55
9.80
9.55
9.70
9.40
9.80
9.80
9.40
9.65
10.30
NONE
CK5A/CK5BA060
CK5A/CK5BX060
F(A,B)4AN(F,B,C)060
FB4ANB070
NONE
NONE
TDR
TDR
—
060-E
FC4BNB070
TDR & TXV
TDR & TXV
NONE
—
—
11.00
—
FC4BN(F,B)060
FG3AAA060
—
11.00
—
FK4CNB006
TDR & TXV
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
CC5A/CD5AW060
CK5A/CK5BW060
56,500
56,500
TDR
TDR
11.80
11.80
—
—
11.80
11.80
10.30
10.30
* Tested Combination
† In most cases, only 1 method should be used to achieve TDR function. Using more than 1 method in a system may cause degradation in performance. Use
either the accessory Time-Delay Relay KAATD0101TDR or a furnace equipped with TDR. All Bryant furnaces are equipped with TDR except for the 394HAD.
‡ Based on computer simulation. TXV must be hard shutoff type.
NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.
2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other
combinations are determined under DOE computer simulation procedures.
3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.
4. Minimum outdoor operating ambient in cooling mode is 55°F (12.8°C), maximum 125°F (51.7°C).
—11—
DETAILED COOLING CAPACITIES*
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
System
Total
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
CFM
EWB
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
594D018-E Outdoor Section With CK5A/CK5BA024 Indoor Section
72
67
62
57
19.6
18.0
16.5
15.9
9.74
12.4
14.9
15.9
1.48
1.46
1.44
1.43
18.9
17.3
15.9
15.4
9.46
12.1
14.6
15.4
1.66
1.63
1.61
1.60
18.1
16.6
15.2
14.8
9.17
11.8
14.3
14.8
1.85
1.82
1.80
1.79
17.4
15.9
14.5
14.2
8.90
11.5
13.9
14.2
2.00
2.00
2.00
2.00
16.6
15.1
13.8
13.6
8.60
11.2
13.5
13.6
2.33
2.28
2.25
2.26
525
600
675
72
67
62
57
19.9
18.3
16.8
16.4
10.1
13.1
15.9
16.4
1.51
1.49
1.46
1.46
19.2
17.6
16.2
15.9
9.86
12.8
15.6
15.9
1.69
1.66
1.65
1.64
18.4
16.9
15.5
15.3
9.57
12.5
15.2
15.3
1.88
1.86
1.84
1.83
17.6
16.1
14.8
14.7
9.30
12.2
14.7
14.7
2.10
2.00
2.00
2.00
16.7
15.3
14.1
14.1
9.01
11.9
14.1
14.1
2.36
2.30
2.28
2.29
72
67
62
57
20.1
18.6
17.1
16.9
10.5
13.8
16.7
16.9
1.54
1.52
1.51
1.49
19.3
17.9
16.4
16.4
10.2
13.5
16.3
16.4
1.72
1.70
1.68
1.68
18.6
17.1
15.8
15.8
9.98
13.2
15.8
15.8
1.92
1.89
1.87
1.87
17.7
16.3
15.1
15.1
9.68
12.9
15.1
15.1
2.10
2.10
2.00
2.00
16.9
15.4
14.4
14.5
9.38
12.6
14.4
14.5
2.38
2.33
2.31
2.32
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Indoor
Section
Size
Capacity
0.98
1.00
1.00
1.00
1.00
0.98
1.00
1.00
0.95
1.00
1.00
0.97
1.00
0.97
Power
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.98
0.99
1.01
0.96
1.00
1.00
Section
Size
001
002
Capacity
1.02
Power
CC5A/CD5AA
018
024
024
024
024
018
024
024
018
024
024
018
024
024
FK4CNF
0.91
0.91
1.02
CC5A/CD5AW
CE3AA
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
CC5A/CD5AA
018
024
018
024
0.97
1.00
0.97
1.00
0.90
0.90
0.90
0.90
CK3BA
CK5A/CK5BA
CK5A/CK5BA
CK5A/CK5BW
F(A,B)4AN(F,C)
COILS + 355MAV042060 VARIABLE SPEED FURNACE
CC5A/CD5AW
CK5A/CK5BW
024
024
1.00
1.00
0.93
0.93
FC4BNF
COILS + 355MAV042080 VARIABLE SPEED FURNACE
FF1(B,C,D)NA
CC5A/CD5AW
CK5A/CK5AW
024
024
—
1.00
1.00
—
0.92
0.92
—
FG3AAA
See notes on page 18.
—12—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
System
Total
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
CFM
EWB
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
594D024-E Outdoor Section With CC5A/CD5AA030 Indoor Section
72
67
62
57
25.7
23.6
21.6
20.8
12.8
16.3
19.7
20.8
2.11
2.08
2.06
2.05
24.7
22.7
20.8
20.1
12.4
15.9
19.3
20.1
2.34
2.30
2.27
2.25
23.7
21.8
19.9
19.4
12.1
15.5
18.8
19.4
2.59
2.55
2.52
2.49
22.7
20.8
19.0
18.7
11.7
15.2
18.4
18.7
2.8
2.8
2.7
2.7
21.6
19.8
18.1
17.9
11.3
14.8
17.8
17.9
3.17
3.13
3.10
3.07
700
800
900
72
67
62
57
26.0
23.9
22.0
21.5
13.3
17.3
20.9
21.5
2.15
2.13
2.10
2.09
25.0
23.0
21.1
20.8
12.9
16.9
20.4
20.8
2.38
2.35
2.32
2.31
24.0
22.0
20.2
20.1
12.6
16.5
19.9
20.1
2.63
2.59
2.56
2.56
22.9
21.0
19.3
19.3
12.2
16.1
19.3
19.3
2.9
2.8
2.8
2.8
21.8
20.0
18.5
18.5
11.8
15.7
18.5
18.5
3.21
3.17
3.14
3.14
72
67
62
57
26.3
24.2
22.3
22.1
13.8
18.2
22.0
22.1
2.19
2.17
2.14
2.14
25.3
23.2
21.4
21.5
13.5
17.8
21.4
21.5
2.42
2.39
2.36
2.37
24.2
22.2
20.6
20.6
13.1
17.4
20.6
20.6
2.67
2.63
2.60
2.60
23.1
21.2
19.8
19.8
12.7
17.0
19.8
19.8
2.9
2.9
2.8
2.8
21.9
20.1
19.0
19.0
12.3
16.6
19.0
19.0
3.25
3.21
3.18
3.18
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Indoor
Section
Size
Capacity
1.00
1.00
1.00
1.01
1.00
1.01
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.02
1.00
1.02
1.00
1.02
Power
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.99
1.00
0.99
1.01
1.01
Section
FG3AAA
FK4CNF
Size
024
001
002
003
Capacity
0.98
Power
CC5A/CD5AA
CC5A/CD5AW
CE3AA
024
030
024
030
024
030
024
024
024
030
024
030
024
024
030
024
030
024
030
1.00
0.94
0.94
0.91
1.04
1.05
1.06
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
CC5A/CD5AA
CE3AA
030
030
030
1.01
1.01
1.01
0.92
0.92
0.92
CF5AA
CG5AA
CK3BA
CK5A/CK5BA
COILS + 355MAV042040 VARIABLE SPEED FURNACE
CC5A/CD5AA
CK5A/CK5BA
030
030
1.01
1.01
0.94
0.94
CK5A/CK5BA
COILS + 355MAV042060 VARIABLE SPEED FURNACE
CK5A/CK5BW
F(A,B)4AN(F,C)
CC5A/CD5AA
CK5A/CK5BA
030
030
1.01
1.01
0.94
0.94
COILS + 355MAV042080 VARIABLE SPEED FURNACE
FC4BNF
CC5A/CD5AA
CK5A/CK5BA
030
030
—
1.01
1.01
—
0.94
0.94
—
FF1(B,C,D)NA
See notes on page 18.
—13—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
System
Total
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
CFM
EWB
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
594D030-E Outdoor Section With CC5A/CD5AA036 Indoor Section
72
67
62
57
32.5
29.7
27.1
26.1
16.1
20.4
24.5
26.1
2.58
2.59
2.62
2.64
31.2
28.5
26.0
25.1
15.6
19.9
24.0
25.1
2.97
2.99
3.01
3.04
29.8
27.2
24.8
24.1
15.1
19.3
23.3
24.1
3.42
3.43
3.46
3.47
28.3
25.7
23.4
23.0
14.5
18.7
22.6
23.0
3.9
3.9
4.0
4.0
26.3
23.6
21.4
21.4
13.8
17.9
21.4
21.4
5.04
5.11
5.01
5.03
875
1000
1125
72
67
62
57
33.0
30.2
27.7
27.0
16.8
21.6
26.1
27.0
2.61
2.62
2.64
2.66
31.7
29.0
26.5
26.1
16.3
21.1
25.5
26.1
3.00
3.02
3.04
3.06
30.2
27.6
25.3
25.0
15.8
20.6
24.8
25.0
3.44
3.46
3.48
3.50
28.7
26.1
23.9
23.8
15.2
20.0
23.8
23.8
4.0
4.0
4.1
4.0
26.7
24.0
22.1
22.2
14.5
19.1
22.1
22.2
5.04
5.12
5.12
5.07
72
67
62
57
33.4
30.6
28.2
27.9
17.4
22.8
27.6
27.9
2.64
2.66
2.67
2.68
32.0
29.4
27.0
26.9
17.0
22.3
26.8
26.9
3.03
3.05
3.07
3.08
30.6
28.0
25.8
25.8
16.5
21.7
25.8
25.8
3.52
3.54
3.56
3.58
29.0
26.4
24.5
24.6
15.9
21.1
24.5
24.6
4.0
4.1
4.1
4.1
27.0
24.3
22.6
22.8
15.2
20.3
22.6
22.8
5.07
5.15
5.34
5.18
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Indoor
Section
Size
Capacity
0.97
1.00
0.97
1.00
0.98
0.99
1.00
0.97
1.00
0.97
1.00
0.97
1.00
0.97
0.99
0.97
0.99
0.98
0.99
—
Power
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.99
1.01
0.99
1.01
1.00
1.00
—
Section
Size
001
002
003
Capacity
1.01
Power
CC5A/CD5AA
030
036
030
036
030
036
036
030
036
030
036
030
036
030
036
030
036
030
036
—
FK4CNF
0.96
0.96
0.92
1.01
CC5A/CD5AW
CD5AW
1.02
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
CE3AA
CC5A/CD5AA
CE3AA
036
036
036
1.01
1.00
1.01
0.92
0.93
0.93
CF5AA
CK3BA
CK5A/CK5BA
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE
CC5A/CD5AA
CE3AA
036
036
036
1.01
1.00
1.01
0.92
0.93
0.92
CK5A/CK5BA
CK5A/CK5BW
F(A,B)4AN(F,C)
FC4BNF
CK5A/CK5BA
COILS + 355MAV042040 VARIABLE SPEED FURNACE
CC5A/CD5AA
CK5A/CK5BA
036
036
1.01
1.01
0.94
0.94
COILS + 355MAV042060 VARIABLE SPEED FURNACE
CC5A/CD5AA
CK5A/CK5BA
036
036
1.01
1.01
0.94
0.96
FF1(B,C,D)NA
FG3AAA
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CC5A/CD5AA
CK5A/CK5BA
036
036
1.01
1.01
0.94
0.94
See notes on page 18.
—14—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
System
Total
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
CFM
EWB
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
594D036-E Outdoor Section With CC5A/CD5AA042 Indoor Section
72
67
62
57
39.1
35.9
32.9
31.6
19.4
24.7
29.8
31.6
3.13
3.10
3.08
3.08
37.5
34.5
31.6
30.6
18.8
24.1
29.2
30.6
3.47
3.44
3.42
3.41
35.9
33.0
30.2
29.5
18.3
23.5
28.5
29.5
3.84
3.81
3.79
3.78
34.3
31.4
28.8
28.4
17.7
22.9
27.7
28.4
4.2
4.2
4.1
4.1
32.6
29.8
27.3
27.1
17.7
22.2
26.9
27.1
4.69
4.64
4.61
4.57
1050
1200
1350
72
67
62
57
39.6
36.5
33.5
32.8
20.2
26.2
31.8
32.8
3.19
3.16
3.14
3.14
38.1
35.0
32.2
31.7
19.7
25.6
31.0
31.7
3.53
3.50
3.48
3.48
36.4
33.5
30.8
30.5
19.1
25.0
30.2
30.5
3.91
3.87
3.84
3.85
34.7
31.8
29.4
29.3
18.5
24.4
29.3
29.3
4.3
4.2
4.2
4.2
32.9
30.2
28.0
27.9
17.9
23.7
28.0
27.9
4.75
4.70
4.66
4.64
72
67
62
57
40.0
36.9
34.0
33.7
21.0
27.6
33.4
33.7
3.25
3.22
3.20
3.20
38.4
35.3
32.7
32.6
20.5
27.0
32.5
32.6
3.59
3.56
3.53
3.54
36.7
33.8
31.3
31.3
19.9
26.4
31.3
31.3
3.96
3.93
3.90
3.91
34.9
32.1
30.1
30.1
19.3
25.8
30.1
30.1
4.3
4.3
4.3
4.3
33.1
30.4
28.7
28.6
18.6
25.1
28.7
28.6
4.80
4.76
4.73
4.71
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Indoor
Section
CE3AA
Section
Size
Capacity
1.00
1.00
0.99
1.00
0.98
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
0.99
0.98
1.00
1.00
1.05
0.98
0.98
1.03
0.99
0.99
1.00
1.03
Power
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.02
1.01
1.01
1.00
1.02
1.00
0.93
0.98
0.98
0.93
0.94
Size
042
042
Capacity
0.99
Power
CC5A/CD5AA
036
042
042
036
036
042
036
036
036
042
036
042
036
042
036
042
042
054
036
036
006
001
002
003
005
0.95
0.94
CK5A/CK5BA
0.99
CC5A/CD5AW
CD5AW
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE
CC5A/CD5AA
CE3AA
042
042
042
0.99
0.99
0.99
0.94
0.95
0.94
CE3AA
CK5A/CK5BA
CF5AA
CG5AA
CK3BA
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
CC5A/CD5AA
CE3AA
042
042
042
0.99
0.99
0.99
0.94
0.95
0.94
CK5A/CK5BA
CK5A/CK5BA
CK5A/CK5BW
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE
CC5A/CD5AA
CE3AA
042
042
042
0.99
0.99
0.99
0.94
0.95
0.94
CK5A/CK5BA
F(A,B)4AN(F,C)
F(A,B)4AN(F,B,C)
FC4BN(F,B)
FC4BNB
COILS + 355MAV042040 VARIABLE SPEED FURNACE
CC5A/CD5AA
CK5A/CK5BA
042
042
0.99
0.99
0.93
0.93
COILS + 355MAV042060 VARIABLE SPEED FURNACE
FC4BNF
CC5A/CD5AA
CK5A/CK5BA
042
042
0.99
0.99
0.93
0.93
FG3AAA
FK4CNB
COILS + 355MAV042080 VARIABLE SPEED FURNACE
FK4CNF
CC5A/CD5AA
CK5A/CK5BA
042
042
0.99
0.99
0.93
0.93
COILS + 355MAV060100 VARIABLE SPEED FURNACE
CC5A/CD5AA
CK5A/CK5BA
042
042
—
0.99
0.99
—
0.93
0.93
—
COILS + 333(B,J)AV036060 VARIABLE SPEED FURNACE
CC5A/CD5AA
042
0.99
0.94
See notes on page 18.
—15—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
System
Total
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
CFM
EWB
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
594D042-E Outdoor Section With CC5A/CD5AA048 Indoor Section
72
67
62
57
45.8
42.0
38.4
36.6
22.5
28.4
34.2
36.6
3.61
3.57
3.54
3.53
44.0
40.4
36.9
35.4
21.9
27.8
33.5
35.4
3.99
3.95
3.91
3.91
42.3
38.7
35.4
34.2
21.2
27.1
32.7
34.2
4.42‘
4.38
4.34
4.33
40.4
37.1
33.8
33.0
20.5
26.4
32.0
33.0
4.9
4.8
4.8
4.8
38.5
35.3
32.3
31.8
19.8
25.7
31.1
31.8
5.44
5.40
5.36
5.36
1225
1400
1575
72
67
62
57
46.5
42.7
39.1
37.9
23.4
30.0
36.4
37.9
3.68
3.64
3.61
3.60
44.7
41.0
37.5
36.6
22.7
29.3
35.5
36.6
4.06
4.02
3.98
3.98
42.8
39.3
35.9
35.4
22.1
28.7
34.7
35.4
4.49
4.45
4.41
4.41
40.9
37.5
34.4
34.1
21.4
27.9
33.8
34.1
4.9
4.9
4.8
4.8
38.9
35.7
32.8
32.7
20.7
27.2
32.7
32.7
5.51
5.46
5.42
5.43
72
67
62
57
47.0
43.2
39.6
39.0
24.3
31.6
38.3
39.0
3.75
3.71
3.68
3.67
45.1
41.5
38.1
37.7
23.6
30.9
38.3
37.7
4.13
4.09
4.05
4.05
43.2
39.7
36.5
36.4
22.9
30.2
36.3
36.4
4.56
4.51
4.48
4.48
41.3
37.9
35.0
35.0
22.2
29.5
35.0
35.0
5.0
4.9
4.9
4.9
39.2
36.1
33.6
33.6
21.5
28.8
33.6
33.6
5.57
5.53
5.49
5.50
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Indoor
Section
Size
Capacity
1.00
0.99
0.99
1.00
1.00
1.00
1.01
1.01
1.00
1.00
1.00
1.00
0.99
1.00
1.00
1.01
1.00
1.01
1.04
1.00
1.04
Power
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.01
1.02
1.01
1.02
1.00
1.00
0.94
Section
Size
003
005
Capacity
1.00
Power
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
042
048
042
048
048
042
048
048
042
048
042
048
042
048
042
048
042
048
054
048
006
FK4CNF
0.95
0.96
1.02
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE
CD5AA
CE3AA
048
048
048
1.00
1.00
1.00
0.93
0.94
0.93
CD5AA
CE3AA
CK5A/CK5BA
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
CF5AA
CK3BA
CD5AA
CE3AA
048
048
048
1.00
1.00
1.00
0.93
0.94
0.93
CK5A/CK5BA
CK5A/CK5BA
CK5A/CK5BW
F(A,B)4AN(F,B,C)
FC4BN(F,B)
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE
CD5AA
CE3AA
048
048
048
1.00
1.00
1.00
0.93
0.94
0.93
CK5A/CK5BA
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CD5A/CD5BA
CK5A/CK5BA
048
048
1.00
1.00
0.92
0.92
COILS + 355MAV060100 VARIABLE SPEED FURNACE
FC4BNB
FG3AAA
FK4CNB
CD5AA
048
048
—
1.00
1.00
—
0.92
0.92
—
CK5A/CK5BA
See notes on page 18.
—16—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
System
Total
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
CFM
EWB
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
594D048-E, F Outdoor Section With CC5A/CD5AA060 Indoor Section
72
67
62
57
52.3
48.3
44.4
42.0
25.6
32.5
39.2
42.0
4.37
4.35
4.34
4.29
50.2
46.3
42.5
40.5
24.8
31.7
38.3
40.5
4.90
4.87
4.86
4.81
47.9
44.2
40.6
39.0
24.0
30.8
37.3
39.0
5.48
5.45
5.43
5.38
45.6
42.1
38.5
37.4
23.1
29.9
36.2
37.4
6.11
6.08
6.05
5.99
43.1
39.8
36.5
35.7
22.2
29.0
35.1
35.7
6.78
6.73
6.70
6.64
1500
1700
1800
72
67
62
57
53.1
49.1
45.1
43.4
26.6
34.2
41.5
43.4
4.45
4.42
4.41
4.37
50.8
47.0
43.2
41.8
25.8
33.4
40.5
41.8
4.97
4.95
4.93
4.89
48.5
44.8
41.2
40.2
24.9
32.5
39.4
40.2
5.55
5.52
5.50
5.46
46.1
42.5
39.1
38.5
24.1
31.6
38.2
38.5
6.19
6.15
6.12
6.08
43.5
40.2
37.1
36.8
23.1
30.6
36.8
36.8
6.86
6.81
6.78
6.73
72
67
62
57
53.4
49.3
45.4
44.0
27.0
35.0
42.5
44.0
4.49
4.46
4.44
4.41
51.1
47.3
43.5
42.4
26.2
34.2
41.5
42.4
5.01
4.98
4.97
4.93
48.7
45.1
41.5
40.8
25.4
33.3
40.3
40.8
5.59
5.56
5.54
5.50
46.3
42.8
39.4
39.1
24.5
32.4
39.0
39.1
6.22
6.19
6.16
6.12
43.7
40.4
37.4
37.3
23.6
31.4
37.4
37.3
6.90
6.85
6.82
6.78
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Section
Indoor
Section
Size
Capacity
1.00
0.96
0.98
1.03
0.99
0.99
1.03
0.99
0.99
1.00
0.99
1.00
0.96
1.00
0.99
1.00
0.99
1.03
0.99
1.03
1.03
1.00
1.03
1.03
0.98
1.01
1.04
1.03
Power
1.00
0.99
1.00
1.00
1.00
1.00
1.00
0.99
1.00
1.00
1.00
1.00
0.98
1.00
1.00
1.00
1.00
1.00
1.02
1.03
1.02
1.02
1.03
1.02
1.00
1.00
0.94
0.95
Size
Capacity
Power
0.94
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
060
048
048
060
048
048
060
048
048
060
048
060
048
060
048
060
048
060
048
060
070
048
060
070
048
060
006
005
CK5A/CK5BX
060
1.00
COILS + 333(B,J)AV060120 VARIABLE SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AW
060
048
060
060
060
048
060
0.99
0.98
1.00
0.99
0.99
0.98
1.00
0.95
0.95
0.95
0.95
0.95
0.95
0.95
CD5AA
CE3AA
CK3BA
CK5A/CK5BA
CK5A/CK5BW
CK5A/CK5BX
CF5AA
CK3BA
COILS + 355MAV042080 VARIABLE SPEED FURNACE
CK5A/CK5BA
CK5A/CK5BN
CK5A/CK5BT
CD5AA
CK3BA
048
048
048
0.98
0.98
0.98
0.97
0.97
0.97
CK5A/CK5BA
COILS + 355MAV060080 VARIABLE SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AW
CD5AA
060
060
048
048
060
060
048
0.98
1.00
0.98
0.98
0.99
1.00
0.98
0.98
0.98
0.98
0.98
0.98
0.98
0.98
CK5A/CK5BW
CK5A/CK5BX
CK3BA
F(A,B)4AN(F,B,C)
CK5A/CK5BA
CK5A/CK5BX
CK5ACK5BA
FB4ANB
FC4BN(F,B)
COILS + 355MAV060100 VARIABLE SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AC
CC5A/CD5AW
CD5AA
060
048
060
048
048
060
048
060
060
0.98
0.96
1.00
0.98
0.98
0.99
0.98
0.98
1.00
0.96
0.97
0.96
0.96
0.96
0.96
0.96
0.96
0.96
FC4BNB
FG3AAA
FK4CNB
FK4CNF
CK3BA
COILS + 333(B,J)AV048080 VARIABLE SPEED FURNACE
CK5A/CK5BA
CK5A/CK5BA
CK5A/CK5BX
CC5A/CD5AC
CD5AA
048
048
048
048
0.96
0.98
0.98
0.98
0.97
0.97
0.97
0.97
CK3BA
COILS + 355MAV060120 VARIABLE SPEED FURNACE
CK5A/CK5BA
CC5A/CD5AA
CC5A/CD5AW
060
048
060
060
060
048
060
—
0.98
0.98
1.00
0.99
0.98
0.98
1.00
—
0.96
0.96
0.96
0.96
0.96
0.96
0.96
—
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
CC5A/CD5AA
CC5A/CD5AW
060
048
060
060
060
048
1.00
0.98
1.00
1.00
1.00
0.98
0.94
0.94
0.94
0.94
0.94
0.94
CK3BA
CK5A/CK5BA
CK5A/CK5BW
CK5A/CK5BX
CK3BA
CK5A/CK5BA
CK5A/CK5BW
See notes on page 18.
—17—
DETAILED COOLING CAPACITIES* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
EVAPORATOR
AIR
85
Capacity
95
Capacity
105
Capacity
115
Capacity
125
Capacity
Total
Total
System
Total
Total
System
Total
MBtuh†
MBtuh†
MBtuh†
MBtuh†
MBtuh†
System
System
System
CFM
EWB
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
Total Sens‡ Kw**
594D060-E Outdoor Section With CC5A/CD5AW060 Indoor Section
72
67
62
57
63.4
57.8
52.4
50.2
31.4
39.6
47.6
50.2
5.42
5.36
5.28
5.20
61.0
55.4
49.9
48.2
30.4
38.6
46.4
48.2
5.88
5.79
5.68
5.59
58.2
52.5
46.9
45.9
29.4
37.5
44.8
45.9
6.35
6.21
6.02
5.93
54.9
49.0
43.4
43.2
28.2
36.1
42.8
43.2
6.7
6.5
6.2
6.2
50.9
44.8
39.7
40.1
26.8
34.4
39.7
40.1
7.13
6.76
6.37
6.37
1750
2000
2250
72
67
62
57
64.7
59.0
53.6
52.2
32.8
42.0
50.7
52.2
5.44
5.38
5.31
5.24
62.1
56.5
51.1
50.3
31.8
41.0
49.4
50.3
5.91
5.82
5.72
5.65
59.3
53.6
48.3
48.0
30.8
39.9
47.6
48.0
6.38
6.26
6.10
6.03
56.0
50.2
45.1
45.4
29.7
38.5
45.1
45.4
6.8
6.6
6.3
6.3
52.1
46.1
41.9
42.3
28.3
37.0
41.9
42.3
7.22
6.89
6.59
6.57
72
67
62
57
65.7
60.0
54.6
54.0
34.1
44.4
53.4
54.0
5.34
5.28
5.34
5.27
62.9
57.4
52.2
52.0
33.1
43.3
51.8
52.0
5.93
5.86
5.77
5.69
60.1
54.5
49.6
49.8
32.1
42.2
49.6
49.8
6.42
6.30
6.17
6.10
56.9
51.2
46.9
47.2
31.0
40.9
46.9
47.2
6.8
6.7
6.5
6.4
53.0
47.0
43.7
44.0
29.7
39.3
43.7
44.0
7.30
7.00
6.76
6.74
Multipliers for Determining the Performance With Other Indoor Sections
Cooling
Cooling
Indoor
Indoor
Section
Size
Capacity
0.96
Power
0.98
1.00
1.00
0.98
1.00
1.04
1.02
Section
FC4BNB
FC4BN(F,B)
FG3AAA
FK4CNB
Size
070
060
060
006
Capacity
1.02
Power
CC5A/CD5AA
CC5A/CD5AW
CE3AA
060
060
060
060
060
060
070
1.02
1.04
1.00
0.97
1.00
1.01
1.00
0.99
CK5A/CK5BA
CK5A/CK5BX
F(A,B)4AN(F,B,C)
FB4ANB
0.96
1.02
1.00
COILS + 333(B,J)AV060100 VARIABLE SPEED FURNACE
1.01
CC5A/CD5AW
CK5A/CK5BW
060
060
1.00
1.00
0.94
0.94
1.02
*
Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI Standard 210/240-94.If additional tubing length and/or indoor
unit is located above outdoor unit, a slight variation in capacity may occur.
†
‡
Total and sensible capacities are net capacities. Blower motor heat has been subtracted.
Sensible capacities shown are based on 80°F (27°C) entering air at the indoor coil. For sensible capacities at other than 80°F (27°C), deduct 835 Btuh
(245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80°F (27°C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air
per degree above 80°F (27°C). When the required data falls between the published data, interpolation may be performed.
** Unit kw is total of indoor and outdoor unit kilowatts.
—18—
CONDENSER ONLY RATINGS*
CONDENSER ENTERING AIR TEMPERATURES °F
SST
°F
55
65
75
85
95
105
115
594D018-E
16.9
77.1
16.2
86.9
15.4
96.8
1.07
14.6
107.0
1.22
13.8
116.00
1.38
12.9
126.0
1.55
12.0
136.0
1.74
TCG
SDT
KW
30
35
40
45
50
55
0.809
0.930
18.6
78.3
0.824
17.8
88.0
0.944
16.9
97.8
1.08
16.1
108.0
1.23
15.2
117.
1.40
14.3
127.0
1.57
13.4
137.0
1.77
TCG
SDT
KW
20.3
79.8
0.841
19.4
89.4
0.962
18.6
99.2
1.10
17.7
109.0
1.25
16.7
119.0
1.42
15.8
128.0
1.60
14.8
138.0
1.79
TCG
SDT
KW
22.1
81.6
0.863
21.2
91.0
0.983
20.3
101.0
1.12
19.3
110.0
1.27
18.3
120.0
1.44
17.3
130.0
1.62
16.3
139.0
1.82
TCG
SDT
KW
24.0
83.5
0.887
23.1
92.8
1.01
22.1
102.0
1.15
21.1
112.0
1.30
20.0
122.0
1.47
19.0
131.0
1.65
17.8
141.0
1.85
TCG
SDT
KW
26.1
85.5
0.914
25.1
94.7
1.03
24.0
104.0
1.17
22.9
114.0
1.33
21.8
123.0
1.50
20.7
133.0
1.68
19.5
142.0
1.89
TCG
SDT
KW
594D024-E
TCG
SDT
KW
22.1
81.1
1.25
21.1
90.3
1.40
20.1
99.6
1.57
19.0
109.0
1.75
17.8
119.0
1.96
16.8
128.0
2.18
15.8
138.0
2.44
30
35
40
45
50
55
TCG
SDT
KW
24.2
83.1
1.26
23.2
92.3
1.42
22.1
102.0
1.59
21.0
111.0
1.78
19.8
120.0
1.99
18.6
130.0
2.21
17.5
139.0
2.47
TCG
SDT
KW
26.4
85.3
1.28
25.4
94.4
1.44
24.3
104.0
1.62
23.1
113.0
1.81
21.8
122.0
2.02
20.6
131.0
2.25
19.3
141.0
2.51
TCG
SDT
KW
28.6
87.6
1.29
27.7
96.6
1.46
26.5
106.0
1.64
25.3
115.0
1.84
24.0
124.0
2.05
22.6
133.0
2.29
21.3
143.0
2.55
TCG
SDT
KW
31.0
90.0
1.30
30.1
99.0
1.48
28.9
108.0
1.66
27.6
117.0
1.87
26.3
126.0
2.09
24.8
135.0
2.33
23.4
145.0
2.60
TCG
SDT
KW
33.5
92.7
1.32
32.5
101.0
1.49
31.4
110.0
1.69
30.0
120.0
1.90
28.6
129.0
2.13
27.1
138.0
2.38
25.6
147.0
2.65
594D030-E
TCG
SDT
KW
28.3
80.4
1.47
27.0
90.3
1.72
25.7
100.0
1.99
24.2
110.0
2.30
22.8
120.0
2.63
21.2
130.0
2.99
19.7
140.0
3.34
30
35
40
45
50
55
TCG
SDT
KW
31.0
82.0
1.46
29.6
91.9
1.71
28.2
102.0
1.99
26.7
112.0
2.30
25.1
122.0
2.64
23.5
132.0
3.00
21.8
142.0
3.39
TCG
SDT
KW
33.9
83.8
1.45
32.4
93.6
1.70
30.9
104.0
1.99
29.3
113.0
2.30
27.6
123.0
2.65
25.9
133.0
3.02
24.1
144.0
3.42
TCG
SDT
KW
36.9
85.7
1.44
35.3
95.5
1.70
33.7
105.0
1.98
32.0
115.0
2.30
30.2
125.0
2.66
28.4
135.0
3.04
26.5
145.0
3.45
TCG
SDT
KW
40.1
87.8
1.43
38.4
97.4
1.69
36.7
107.0
1.98
34.9
117.0
2.31
33.0
127.0
2.66
31.0
137.0
3.05
29.0
147.0
3.47
TCG
SDT
KW
43.5
90.0
1.43
41.7
99.7
1.69
39.8
109.0
1.98
37.9
119.0
2.31
35.9
129.0
2.67
33.8
139.0
3.07
31.7
149.0
3.50
594D036-E
TCG
SDT
KW
33.8
77.3
1.87
32.3
87.0
2.11
30.7
96.9
2.37
29.1
107.0
2.66
27.4
117.0
2.98
25.7
126.0
3.32
23.9
136.0
3.68
30
35
40
45
50
55
TCG
SDT
KW
37.0
78.6
1.89
35.4
88.3
2.12
33.8
98.1
2.39
32.0
108.0
2.68
30.3
118.0
3.00
28.4
128.0
3.35
26.6
137.0
3.72
TCG
SDT
KW
40.5
80.3
1.91
38.8
89.8
2.14
37.0
99.5
2.41
35.2
109.0
2.70
33.3
119.0
3.03
31.3
129.0
3.39
29.4
139.0
3.76
TCG
SDT
KW
44.1
82.1
1.93
42.3
91.5
2.17
40.5
101.0
2.44
38.5
111.0
2.73
36.5
121.0
3.06
34.4
130.0
3.42
32.3
140.0
3.81
TCG
SDT
KW
48.0
84.0
1.96
46.1
93.3
2.20
44.1
103.0
2.47
42.0
112.0
2.76
39.9
122.0
3.10
37.7
132.0
3.46
35.4
142.0
3.86
TCG
SDT
KW
52.1
86.1
1.99
50.0
95.3
2.23
47.9
105.0
2.50
45.7
114.0
2.80
43.4
124.0
3.14
41.1
133.0
3.50
38.6
143.0
3.91
See notes on page 20.
—19—
CONDENSER ONLY RATINGS* Continued
CONDENSER ENTERING AIR TEMPERATURES °F
SST
°F
55
65
75
85
95
105
115
594D042-E
TCG
SDT
KW
39.4
77.0
2.17
37.6
86.9
2.43
35.7
96.8
2.72
33.9
107.0
3.04
32.0
117.0
3.40
30.2
127.0
3.81
28.4
137.0
4.26
30
35
40
45
50
55
TCG
SDT
KW
43.3
78.5
2.19
41.4
88.2
2.45
39.4
98.0
2.74
37.4
108.0
3.07
35.4
118.0
3.43
33.4
128.0
3.84
31.4
138.0
4.30
TCG
SDT
KW
47.5
80.0
2.21
45.4
89.7
2.48
43.3
99.5
2.77
41.1
109.0
3.10
39.0
119.0
3.47
36.8
129.0
3.88
34.6
139.0
4.34
TCG
SDT
KW
51.8
81.7
2.24
49.6
91.4
2.51
47.4
101.0
2.80
45.1
111.0
3.14
42.7
121.0
3.51
40.4
131.0
3.92
38.1
141.0
4.39
TCG
SDT
KW
56.4
83.6
2.27
54.1
93.2
2.54
51.7
103.0
2.84
49.2
113.0
3.18
46.7
122.0
3.55
44.2
132.0
3.97
41.7
142.0
4.44
TCG
SDT
KW
61.2
85.6
2.31
58.8
95.1
2.58
56.2
105.0
2.88
53.6
114.0
3.22
51.0
124.0
3.60
48.3
134.0
4.03
45.6
144.0
4.50
594D048-E, F
TCG
SDT
KW
46.0
80.1
2.46
43.8
89.8
2.82
41.6
99.6
3.22
39.3
109.0
3.65
36.9
119.0
4.13
34.4
129.0
4.64
32.0
139.0
5.17
30
35
40
45
50
55
TCG
SDT
KW
50.4
81.9
2.49
48.1
91.6
2.85
45.7
101.0
3.25
43.2
111.0
3.69
40.7
121.0
4.18
38.1
131.0
4.71
35.5
140.0
5.25
TCG
SDT
KW
55.1
83.9
2.52
52.6
93.4
2.88
50.1
103.0
3.29
47.4
113.0
3.74
44.7
123.0
4.23
41.9
132.0
4.77
39.1
142.0
5.34
TCG
SDT
KW
60.0
86.0
2.55
57.4
95.5
2.92
54.7
105.0
3.33
51.9
115.0
3.79
49.0
124.0
4.29
46.0
134.0
4.84
43.0
144.0
5.43
TCG
SDT
KW
65.2
88.3
2.59
62.4
97.7
2.96
59.6
107.0
3.38
56.6
117.0
3.84
53.5
126.0
4.35
50.3
136.0
4.91
47.1
146.0
5.51
TCG
SDT
KW
70.7
90.7
2.64
67.7
100.0
3.01
64.6
109.0
3.43
61.5
119.0
3.90
58.2
128.0
4.42
54.8
138.0
4.98
51.3
148.0
5.60
594D060-E
TCG
SDT
KW
55.1
80.2
3.06
52.7
89.9
3.44
50.1
99.7
3.86
47.4
109.0
4.34
44.8
119.0
4.87
42.2
129.0
5.46
39.5
139.0
6.07
30
35
40
45
50
55
TCG
SDT
KW
60.3
82.1
3.10
57.7
91.8
3.49
55.0
101.0
3.92
52.1
111.0
4.40
49.2
121.0
4.93
46.4
131.0
5.53
43.5
141.0
6.17
TCG
SDT
KW
65.7
84.1
3.16
63.0
93.7
3.55
60.1
103.0
3.99
57.1
113.0
4.47
54.0
123.0
5.01
50.9
133.0
5.61
47.8
143.0
6.27
TCG
SDT
KW
71.4
86.3
3.21
68.6
95.9
3.62
65.6
105.0
4.06
62.3
115.0
4.55
59.0
125.0
5.09
55.6
135.0
5.69
52.3
144.0
6.36
TCG
SDT
KW
77.4
88.6
3.28
74.5
98.1
3.69
71.3
108.0
4.14
67.8
117.0
4.64
64.3
127.0
5.19
60.6
136.0
5.79
57.0
146.0
6.46
TCG
SDT
KW
83.8
91.1
3.35
80.7
101.0
3.77
77.3
110.0
4.23
73.7
120.0
4.74
69.9
129.0
5.29
66.0
139.0
5.90
62.0
148.0
6.58
* ARI listing applies only to systems shown in Performance Data table.
KW — Total Power (Kw)
SDT — Saturated Temperature Leaving Compressor (°F)
SST — Saturated Temperature Entering Compressor (°F)
TCG — Gross Cooling Capacity (1000 Btuh)
—20—
SYSTEM DESIGN SUMMARY
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01 in. wc.
2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55°F (12.8°C).
3. Maximum outdoor operating air temperature is 125°F (51.7°C).
4. For reliable operation, unit should be level in all horizontal planes.
5. Maximum elevation of indoor coil above or below base of outdoor unit is: Indoor coil above = 50 ft. Indoor coil below = 150 ft.
6. For interconnecting refrigerant tube lengths greater than 50 ft, consult Residential Split System Long-Line Application Guidelines available from
equipment distributor.
7. Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft.
8. Not more than 3 ft of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in. vertical
rise to the valve connections at the unit. For buried lines longer than 3 ft, consult your local distributor.
9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.
10. Mix-matches of indoor coil capacity more than 1 size larger than outdoor unit capacity may result in inadequate indoor comfort.
11. Do not apply capillary tube indoor coils to these units.
—21—
MATCHED SYSTEM
A98599
—22—
—23—
Air-Cooled, Split-System
Air Conditioner
GUIDE SPECIFICATIONS
594D
1-1/2 to 5 Tons Nominal
Condenser fan motors will be totally enclosed, 1-phase type
with class B insulation and permanently lubricated bearings.
Shafts will be corrosion resistant.
Fan blades will be statically and dynamically balanced.
Condenser fan openings will be equipped with steel wire safety
guards.
GENERAL
System Description
Outdoor-mounted, air-cooled, split-system air conditioner unit
suitable for ground or rooftop installation. Unit consists of a her-
metic compressor, an air-cooled coil, propeller-type condenser
fan, and a control box. Unit will discharge supply air upward as
shown on contract drawings. Unit will be used in a refrigeration
circuit to match up to a packaged fan coil or coil unit.
Compressor
Compressor will be hermetically sealed.
Compressor will be mounted on rubber vibration isolators.
Condenser Coil
Quality Assurance
Unit will be rated in accordance with the latest edition of ARI
Standard 210.
Unit will be certified for capacity, efficiency, and listed in the latest
ARI directory.
Unit construction will comply with latest edition of ANSI/
ASHRAE and with NEC.
Unit will be constructed in accordance with UL standards and
will carry the UL label of approval. Unit will have c-UL approval.
Unit cabinet will be capable of withstanding Federal Test Method
Standard No. 141 (Method 6061) 500-hr salt spray test.
Air-cooled condenser coils will be leak tested at 150 psig and
pressure tested at 300 psig.
Condenser coil will be air cooled.
Coil will be constructed of aluminum fins mechanically bonded
to copper tubes which are then cleaned, dehydrated, and
sealed.
Refrigeration Components
Refrigeration circuit components will include liquid-line shutoff
valve with sweat connections, suction line shutoff valves with
sweat connections, system charge of R22 (R-410A) refrigerant,
and compressor oil.
Operating Characteristics
The capacity of the unit will meet or exceed _____ Btuh at a
suction temperature of _____ °F.The power consumption at full
load will not exceed _____ kw.
Combination of the unit and the evaporator or fan coil unit will
have a total net cooling capacity of _____ Btuh or greater at
conditions of _____ CFM entering air temperature at the
evaporator at _____ °F wet bulb and _____ °F dry bulb, and air
entering the unit at _____ °F.
Unit constructed in ISO 9001 approved facility.
Delivery, Storage, and Handling
Unit will be shipped as single package only and is stored and
handled per unit manufacturer’s recommendations.
Warranty (for inclusion by specifying engineer)
U.S. and Canada only.
The system will have an SEER of _____ Btuh/watt or greater at
DOE conditions.
PRODUCTS
Equipment
Electrical Requirements
Nominal unit electrical characteristics will be _____ v, single
phase, 60 hertz. The unit will be capable of satisfactory opera-
tion within voltage limits of _____ v to _____ v.
Unit electrical power will be single point connection.
Control circuit will be 24v.
Factory assembled, single piece, air-cooled air conditioner unit.
Contained within the unit enclosure will be all factory wiring,
piping, controls, compressor, refrigerant charge (R22), and
special features required prior to field start-up.
Unit Cabinet
Unit cabinet will be constructed of galvanized steel, bonderized,
and coated with a powder coat paint.
Fans
Condenser fan will be direct-drive propeller type, discharging air
upward.
Special Features
Refer to section of this literature identifying accessories and
descriptions for specific features and available enhancements.